PI Tuning for Integrating (Level-Type) Processes (SIMC)

PI settings for an integrating process such as level or drum pressure by Skogestad's SIMC rule from the integrating rate and dead time, with arrest time.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Level 0.01 %/s per %, θ 5 sAveraging level, τc 300 s

Slope of the PV trend after a step in output, divided by the step; choose 1/min for a rate read per minute.

Results

Skogestad (2003) SIMC rule for integrating processes. For surge-tank averaging level control use a larger τ_c to let the level swing and smooth the outlet flow.

Controller gain10.000
Integral time40.000s
Approximate arrest time 2(τ_c + θ) (rule of thumb)20.000s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Level 0.01 %/s per %, θ 5 s. The inputs, in the units selected above:

InputValue
Integrating rate (% PV per % output, per unit time)0.010000 1/s
Dead time5.0000 s
Closed-loop time constant (default = dead time)5.0000 s

Applying the formula below gives:

ResultValue
Controller gain10.000
Integral time40.000 s
Approximate arrest time 2(τ_c + θ) (rule of thumb)20.000 s

Open this example in the calculator and change any input.

Formula

\(K_c = \frac{1}{k'(\tau_c + \theta)}, \quad T_i = 4(\tau_c + \theta), \quad t_{arrest} \approx 2(\tau_c + \theta)\)

Variables

Symbol Meaning SI unit
\(k'\) Integrating rate (% PV per % output, per unit time) 1/s
\(\theta\) Dead time s
\(\tau_c\) Closed-loop time constant (default = dead time) s
\(K_c\) Controller gain -
\(T_i\) Integral time s
\(t_{arrest}\) Approximate arrest time 2(τ_c + θ) (rule of thumb) s

Method and standards

SIMC rule.

Where it is used

  • Drum, deaerator and tank level loops.
  • Averaging level control.

Common mistakes

  • Fast integral on level (cycling).
  • Measuring k' in engineering units then using % gain.

Assumptions and limits

  • Pure integrator with dead time.
  • k' is a rate (per second, or per minute with the unit chosen); a rate read per minute and entered as per second would make K_c 60 times too small.
  • The arrest time 2(τ_c + θ) is a rule-of-thumb estimate, not part of the SIMC rules.

References

  • Skogestad (2003)
  • J. Process Control 13: 291 (SIMC rules, integrating processes: K_c = 1/(k'(τ_c + θ)), T_i = 4(τ_c + θ))

Questions and answers

Why are level loops different?

Level has no natural steady state: any mismatch between in- and outflow ramps it. Integral action must be slow or the loop oscillates.

What is arrest time?

How long the controller takes to stop a level ramp after a step disturbance.

What do the defaults represent?

A level ramping 0.01 %/s per % valve with 5 s dead time.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.