Ratio Control: Ratio Setting and Scaled Ratio for Transmitter Spans

Ratio setting between a controlled and a wild flow, and the scaled ratio to enter when the two transmitters have different spans or dp signals.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 5 % dosing, 0–100 wild, 0–10 dosing, linearAir–fuel 15, dp signals 0–2,000 and 0–30,000

Results

Extract square roots before the ratio station where possible; ratio on unextracted dp signals makes the loop gain vary with flow.

Scaled ratio (signal units)0.50000
Controlled flow set point3.0000
Controlled flow set point (% of span)30.000%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5 % dosing, 0–100 wild, 0–10 dosing, linear. The inputs, in the units selected above:

InputValue
Required ratio controlled/wild flow (engineering units)0.050000 -
Wild flow transmitter span100.00 -
Controlled flow transmitter span10.000 -
Signal typeLinear in flow
Present wild flow (for the set point)60.000 -

Applying the formula below gives:

ResultValue
Scaled ratio (signal units)0.50000
Controlled flow set point3.0000
Controlled flow set point (% of span)30.000 %

Open this example in the calculator and change any input.

Formula

\(R_s = R\frac{S_w}{S_c}\ \text{(linear)}, \quad R_s = \left(R\frac{S_w}{S_c}\right)^2\ \text{(unextracted dp)}\)

Variables

Symbol Meaning SI unit
\(R\) Required ratio controlled/wild flow (engineering units) -
\(S_w\) Wild flow transmitter span -
\(S_c\) Controlled flow transmitter span -
\(\text{signal}\) Signal type -
\(F_w\) Present wild flow (for the set point) -
\(R_s\) Scaled ratio (signal units) -
\(F_c\) Controlled flow set point -
\(y_c\) Controlled flow set point (% of span) -

Method and standards

Signal scaling.

Where it is used

  • Chemical dosing and blending.
  • Combustion air–fuel ratio.

Common mistakes

  • Forgetting square-root signals.
  • Spans in different units.

Assumptions and limits

  • Steady-state ratio.

References

  • Seborg
  • Edgar
  • Mellichamp and Doyle
  • Process Dynamics and Control
  • 4th ed. (Wiley, 2016)
  • ch. 15 (ratio control)

Questions and answers

Why scale the ratio?

The controller works in % of span; if the two transmitters span different ranges, the engineering ratio must be converted.

Where is ratio control used?

Fuel and air, chemical dosing to flow, blending, steam to feed in deaerators.

What do the defaults represent?

Dosing at 5 % of a 0–100 wild flow using a 0–10 dosing transmitter.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.