Worked example
Example: Quarter of full DP, 5 % cut-off. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flow at full-scale DP | 100.00 - |
| Full-scale DP of the transmitter | 250.00 mbar |
| DP reading | 62.500 mbar |
| Low-flow cut-off (share of full flow) | 5.0000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Flow at the DP reading | 50.000 |
| Flow as a share of full scale | 50.000 % |
| Signal of a linear-DP transmitter | 8.0000 mA |
| Signal of a square-root (flow) transmitter | 12.000 mA |
| DP at the low-flow cut-off | 0.62500 mbar |
Open this example in the calculator and change any input.
Formula
\(Q = Q_{max}\sqrt{\frac{\Delta p}{\Delta p_{max}}}, \quad I_{sqrt} = 4 + 16\,\frac{Q}{Q_{max}}\ \text{mA}, \quad \Delta p_c = q_c^2\, \Delta p_{max}\quad (Q = 0,\ I_{sqrt} = 4\ \text{mA when}\ Q/Q_{max} < q_c)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_{max}\) | Flow at full-scale DP | - |
| \(\Delta p_{max}\) | Full-scale DP of the transmitter | Pa |
| \(\Delta p\) | DP reading | Pa |
| \(q_{c}\) | Low-flow cut-off (share of full flow) | - |
| \(Q\) | Flow at the DP reading | - |
| \(Q/Q_{max}\) | Flow as a share of full scale | - |
| \(I_{lin}\) | Signal of a linear-DP transmitter | A |
| \(I_{sqrt}\) | Signal of a square-root (flow) transmitter | A |
| \(\Delta p_c\) | DP at the low-flow cut-off | Pa |
Method and standards
Flow through a fixed restriction goes as the square root of DP.
Where it is used
- Configuring DCS and transmitter square-root extraction.
- Checking flow readings in the field.
Common mistakes
- Extracting the square root twice (transmitter and DCS).
- No cut-off at low flow.
Assumptions and limits
- Constant density and discharge coefficient.
- Below the low-flow cut-off the flow is shown as zero and the square-root signal as 4 mA; Q/Q_max still gives the uncut share.
References
- Q ∝ √Δp for differential-pressure flowmeters (ISO 5167-1 principle)
Questions and answers
What flow does a quarter of full-scale DP mean?
Half the full flow: Q = Q_max √(Δp/Δp_max).
What mA does a square-root transmitter give then?
12 mA; a linear-DP transmitter gives 8 mA.
Why a cut-off?
Near zero DP a little noise is a lot of flow; 5 % flow is only 0.25 % of DP.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.