Worked example
Example: Design 7 bar(a) 30 °C, actual 6 bar(a) 45 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Indicated flow (at design conditions) | 1,000.0 - |
| Design pressure (absolute; shown as gauge, converted with 1.01325 bar) | 5.9867 bar g |
| Design temperature | 30.000 °C |
| Actual pressure (absolute; shown as gauge, converted with 1.01325 bar) | 4.9867 bar g |
| Actual temperature | 45.000 °C |
| Compressibility ratio (design / actual) | 1.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Correction for standard volume or mass flow √(p T_d Z_d / (p_d T Z)) | 0.90373 |
| Corrected standard volume or mass flow | 903.73 |
| Correction for actual volume flow √(p_d T Z / (p T_d Z_d)) | 1.1065 |
| Corrected actual volume flow | 1,106.5 |
Open this example in the calculator and change any input.
Formula
\(Q_N = Q_{ind}\sqrt{\frac{p\, T_d\, Z_d}{p_d\, T\, Z}}, \quad Q_a = Q_{ind}\sqrt{\frac{p_d\, T\, Z}{p\, T_d\, Z_d}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_{ind}\) | Indicated flow (at design conditions) | - |
| \(p_d\) | Design pressure (absolute; shown as gauge, converted with 1.01325 bar) | Pa |
| \(T_d\) | Design temperature | K |
| \(p\) | Actual pressure (absolute; shown as gauge, converted with 1.01325 bar) | Pa |
| \(T\) | Actual temperature | K |
| \(Z_d/Z\) | Compressibility ratio (design / actual) | - |
| \(k_N\) | Correction for standard volume or mass flow √(p T_d Z_d / (p_d T Z)) | - |
| \(Q_N\) | Corrected standard volume or mass flow | - |
| \(k_a\) | Correction for actual volume flow √(p_d T Z / (p T_d Z_d)) | - |
| \(Q_a\) | Corrected actual volume flow | - |
Method and standards
Density correction of the square-root flow equation.
Where it is used
- DCS flow compensation blocks.
- Fuel gas and compressed air metering.
Common mistakes
- Gauge pressure in the ratio.
- Applying the factor squared.
Assumptions and limits
- Ideal gas with a Z ratio; same Δp.
- Pressures are absolute; the gauge display is converted with the standard atmosphere, not the site barometer (enter absolute at altitude).
- Read Q_N if the meter is scaled in standard volume or mass flow, Q_a if it is scaled in actual volume flow.
References
- Ideal-gas density correction of a DP meter: q_m ∝ √(ρ Δp)
Questions and answers
Design 7 bar(a), 30 °C; actual 6 bar(a), 45 °C: how wrong is the reading?
Standard flow factor √(6/7 × 303.15/318.15) = 0.9037: the meter reads 10.7 % high.
Mass or standard volume?
Both take the same factor; actual volume takes the inverse.
Do I need compressibility?
Near ambient, no; at high pressure, yes.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.