FireCADCalc

Flow Nozzle (ISA 1932) Liquid Flow

Liquid flow through an ISA 1932 flow nozzle from differential pressure, pipe and throat bores and fluid properties, with a Reynolds-dependent C.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliserISO 5167 (differential-pressure flow)

Inputs

Examples: 200 mm pipe, 120 mm throat, 25 kPa waterFeedwater 150 mm pipe, 90 mm throat, 60 kPa

Results

Diameter ratio0.60000
Discharge coefficient0.96165
Pipe Reynolds number524,254
Volume flow297.05m³/h
Mass flow296.46t/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 200 mm pipe, 120 mm throat, 25 kPa water. The inputs, in the units selected above:

InputValue
Differential pressure25.000 kPa
Pipe inside diameter200.00 mm
Throat diameter120.00 mm
Density998.00 kg/m³
Viscosity1.0000 cP

Applying the formula below gives:

ResultValue
Diameter ratio0.60000
Discharge coefficient0.96165
Pipe Reynolds number524,254
Volume flow297.05 m³/h
Mass flow296.46 t/h

Open this example in the calculator and change any input.

Formula

\(Q = \frac{C}{\sqrt{1 - \beta^4}}\frac{\pi d^2}{4}\sqrt{\frac{2\Delta p}{\rho}}, \quad C = 0.9900 - 0.2262\beta^{4.1} - (0.00175\beta^2 - 0.0033\beta^{4.15})\left(\frac{10^6}{Re_D}\right)^{1.15}\)

Variables

Symbol Meaning SI unit
\(\Delta p\) Differential pressure Pa
\(D\) Pipe inside diameter m
\(d\) Throat diameter m
\(\rho\) Density kg/m³
\(\mu\) Viscosity Pa·s
\(\beta\) Diameter ratio -
\(C\) Discharge coefficient -
\(Re_D\) Pipe Reynolds number -
\(Q\) Volume flow m³/s
\(\dot m\) Mass flow kg/s

Method and standards

ISA 1932 nozzle.

Where it is used

  • Feedwater and condensate flow.
  • Checking nozzle calibration.

Common mistakes

  • Using an orifice C.
  • Ignoring the range limits.

Assumptions and limits

  • Incompressible flow; standard installation.
  • The range check is 0.3 ≤ β ≤ 0.8 and 2×10⁴ ≤ Re_D ≤ 10⁷. ISO 5167-3 is tighter for β below 0.44 (a higher lower Reynolds-number limit) and for pipes outside about 50–500 mm; a note appears in those cases.

References

  • ISA 1932 nozzle discharge coefficient C = 0.9900 − 0.2262β^4.1 − (0.00175β² − 0.0033β^4.15)(10⁶/Re_D)^1.15 (ISO 5167-3 form)

Questions and answers

Why a nozzle instead of an orifice?

Lower permanent pressure loss than an orifice for the same differential, and it resists erosion: common for boiler feedwater and high-velocity flows.

Why iterate?

The discharge coefficient depends on Reynolds number, which depends on the flow being calculated.

What do the defaults represent?

Water through a 200 mm pipe with a 120 mm throat at 25 kPa differential.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.