Worked example
Example: Process 120 s, disturbance 200 s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Process gain (output per % controller output) | 2.0000 - |
| Process time constant | 120.00 s |
| Process dead time | 20.000 s |
| Disturbance gain | 1.5000 - |
| Disturbance time constant | 200.00 s |
| Disturbance dead time | 30.000 s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Feedforward gain | -0.75000 |
| Lead time | 120.00 s |
| Lag time | 200.00 s |
| Feedforward dead time (0 if not realisable) | 10.000 s |
Open this example in the calculator and change any input.
Formula
\(G_{ff}(s) = -\frac{K_d}{K_p}\frac{\tau_ps + 1}{\tau_ds + 1}e^{-(\theta_d - \theta_p)s}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(K_p\) | Process gain (output per % controller output) | - |
| \(\tau_p\) | Process time constant | s |
| \(\theta_p\) | Process dead time | s |
| \(K_d\) | Disturbance gain | - |
| \(\tau_d\) | Disturbance time constant | s |
| \(\theta_d\) | Disturbance dead time | s |
| \(K_{ff}\) | Feedforward gain | - |
| \(T_{lead}\) | Lead time | s |
| \(T_{lag}\) | Lag time | s |
| \(\theta_{ff}\) | Feedforward dead time (0 if not realisable) | s |
Method and standards
Ideal feedforward from FOPDT models.
Where it is used
- Boiler drum level, deaerator and heater loops.
- Blending and neutralisation.
Common mistakes
- Wrong sign on the gain.
- Removing feedback trim.
Assumptions and limits
- Linear FOPDT models.
- When θ_d < θ_p the feedforward is not realisable; the dead time is set to zero, with a note.
References
- Seborg
- Edgar
- Mellichamp and Doyle
- Process Dynamics and Control
- 4th ed. (Wiley, 2016)
- ch. 15 (feedforward control design from FOPDT models)
Questions and answers
When is feedforward worth it?
When a measurable disturbance (steam flow, feed rate, ambient) upsets the loop faster than feedback can correct.
Why the lead–lag?
It matches the different speeds of the disturbance and manipulated-variable paths; the static gain alone gets the final value right.
What do the defaults represent?
A loop with a 120 s process lag and a slower 200 s disturbance path.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.