SIMC PI Controller Tuning (Skogestad)

PI controller gain and integral time by Skogestad's SIMC rules for a first-order process with dead time, with the closed-loop time constant as the one tuning choice.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Gain 2, 60 s, 10 s dead time, tc = thetaSlow temperature loop: gain 0.8, 600 s, 30 s, tc 30 sFlow loop: gain 1.2, 3 s, 1 s, tc 2 s

τ_c = θ gives fast, robust control; larger values are smoother.

Results

Gain in the units of the process gain (normally % per %); integral time in seconds per repeat.

Controller gain1.5000
Integral time60.000s
Proportional band 1/K_c66.667%
Integral gain (repeats per second × gain)0.025000Hz

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Gain 2, 60 s, 10 s dead time, tc = theta. The inputs, in the units selected above:

InputValue
Process gain (change in output / change in controller output)2.0000 -
Process time constant60.000 s
Dead time10.000 s
Desired closed-loop time constant10.000 s

Applying the formula below gives:

ResultValue
Controller gain1.5000
Integral time60.000 s
Proportional band 1/K_c66.667 %
Integral gain (repeats per second × gain)0.025000 Hz

Open this example in the calculator and change any input.

Formula

\(K_c = \frac{1}{K_p}\, \frac{\tau}{\tau_c + \theta}, \quad \tau_I = \min\left[\tau,\ 4(\tau_c + \theta)\right]\)

Variables

Symbol Meaning SI unit
\(K_p\) Process gain (change in output / change in controller output) -
\(\tau\) Process time constant s
\(\theta\) Dead time s
\(\tau_c\) Desired closed-loop time constant s
\(K_c\) Controller gain -
\(\tau_I\) Integral time s
\(PB\) Proportional band 1/K_c -
\(K_c/\tau_I\) Integral gain (repeats per second × gain) 1/s

Method and standards

SIMC rules from the IMC design for a first-order plus dead-time model.

Where it is used

  • Tuning flow, pressure and temperature loops.
  • Commissioning.

Common mistakes

  • Controller gain in the wrong units.
  • Using τ_c much below θ.

Assumptions and limits

  • First-order plus dead-time model; PI settings only. The SIMC derivative setting for second-order (dominant lag) models is not given here.

References

  • S. Skogestad
  • Simple analytic rules for model reduction and PID controller tuning
  • J. Process Control 13 (2003) 291

Questions and answers

Gain 2, time constant 60 s, dead time 10 s: what PI settings?

With τ_c = θ = 10 s: K_c = 60/(2 × 20) = 1.5 and τ_I = min(60, 80) = 60 s.

What does τ_c do?

It sets how fast the loop responds; larger τ_c is gentler and more robust.

Why the 4(τ_c + θ) limit?

For slow processes it stops the integral time growing so large that disturbances linger.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.