Worked example
Example: 24 V, 12 V lift-off, 22 mA, 250 Ω card, 500 m of 18.5 Ω/km. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Loop supply voltage | 24.000 V |
| Lowest voltage the transmitter needs at its terminals | 12.000 V |
| Highest loop current to allow for (alarm or saturation) | 22.000 mA |
| Input resistance of the receiving card | 250.00 Ω |
| Other loads in the loop (barrier, indicator) | 0 Ω |
| Resistance of one cable core per length | 18.500 Ω/km |
| Cable length, one way | 500.00 m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Largest total loop resistance allowed | 545.45 Ω |
| Actual loop resistance (loads plus both cores) | 268.50 Ω |
| Spare resistance | 276.95 Ω |
| Voltage at the transmitter at the highest current | 18.093 V |
| Longest cable for these loads | 7,985.3 m |
Open this example in the calculator and change any input.
Formula
\(R_{max} = \frac{V_s - V_{min}}{I_{max}}, \quad R_{loop} = R_{in} + R_x + 2 r_c L\)
\(V_t = V_s - I_{max} R_{loop}, \quad L_{max} = \frac{R_{max} - R_{in} - R_x}{2 r_c}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_s\) | Loop supply voltage | V |
| \(V_{min}\) | Lowest voltage the transmitter needs at its terminals | V |
| \(I_{max}\) | Highest loop current to allow for (alarm or saturation) | A |
| \(R_{in}\) | Input resistance of the receiving card | Ω |
| \(R_x\) | Other loads in the loop (barrier, indicator) | Ω |
| \(r_c\) | Resistance of one cable core per length | Ω/m |
| \(L\) | Cable length, one way | m |
| \(R_{max}\) | Largest total loop resistance allowed | Ω |
| \(R_{loop}\) | Actual loop resistance (loads plus both cores) | Ω |
| \(R_{max} - R_{loop}\) | Spare resistance | Ω |
| \(V_t\) | Voltage at the transmitter at the highest current | V |
| \(L_{max}\) | Longest cable for these loads | m |
Method and standards
A two-wire transmitter needs its minimum terminal voltage at the highest loop current; whatever the supply has left over can be dropped across the receiving card, barriers and both cable cores.
Where it is used
- Checking long field loops and loops with barriers.
- Choosing the supply voltage.
- Diagnosing loops that saturate below 20 mA.
Common mistakes
- Counting only one cable core.
- Forgetting HART needs at least 250 Ω in the loop.
- Using 20 mA when fault signalling goes higher.
Assumptions and limits
- Steady current; supply at its lowest tolerance value if you enter it.
- Cable resistance at the value entered: correct it for the hottest conductor temperature (about +0.4 % per K for copper), which reduces the margin.
- With zero cable resistance no length limit is shown.
References
- Two-wire 4–20 mA loop (IEC 60381-1 signal, transmitter load line)
Questions and answers
What load can a 24 V loop drive?
With 12 V lift-off at 22 mA, 545 Ω. A 250 Ω card and 500 m of 18.5 Ω/km cable use 269 Ω, leaving 277 Ω spare.
How far can the cable run?
About 8 km for those loads; a 280 Ω barrier and thinner cable cut it to about 1.6 km.
Why 22 mA and not 20?
Transmitters signal faults above 20 mA (NAMUR NE 43 uses 21 mA and more); the loop must still drive that current.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.