Worked example
Example: 3 m² tank, 2 m span, 20 m³/h valve. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Inflow change for 100 % valve | 20.000 m³/h |
| Tank cross-section | 3.0000 m² |
| Level transmitter span | 2.0000 m |
| Working volume (for residence time) | 6.0000 m³ |
| Normal throughput | 10.000 m³/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Integrating rate (%/s per % of valve) | 9.2593e-04 1/s |
| Time to change the span at full valve imbalance | 18.000 min |
| Residence time at normal throughput | 36.000 min |
Open this example in the calculator and change any input.
Formula
\(k' = \frac{Q_{max}}{AL_s}, \quad t_{fill} = \frac{1}{k'}, \quad \tau_r = \frac{V}{Q_n}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_{max}\) | Inflow change for 100 % valve | m³/s |
| \(A\) | Tank cross-section | m² |
| \(L_s\) | Level transmitter span | m |
| \(V\) | Working volume (for residence time) | m³ |
| \(Q_n\) | Normal throughput | m³/s |
| \(k'\) | Integrating rate (%/s per % of valve) | 1/s |
| \(t_{fill}\) | Time to change the span at full valve imbalance | s |
| \(\tau_r\) | Residence time at normal throughput | s |
Method and standards
Tank mass balance.
Where it is used
- Level loop tuning.
- Choosing tank sizes for surge capacity.
Common mistakes
- Using diameter for area.
- Spans in different units.
Assumptions and limits
- Constant cross-section.
References
- Mass balance of a tank (Seborg, Edgar, Mellichamp and Doyle, Process Dynamics and Control, 4th ed. (Wiley, 2016), ch. 2)
Questions and answers
Why is level integrating?
Level changes at the rate of in-minus-out flow; it keeps changing as long as there is an imbalance.
How is k' measured?
Put the controller in manual, step the valve a few per cent and measure the slope of the level trend.
What do the defaults represent?
A 3 m² tank with a 2 m level span and a 20 m³/h valve.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.