Second-Order System Step Response: Overshoot and Settling Time

Percentage overshoot, peak time, rise time and settling time of an underdamped second-order system from its natural frequency and damping ratio.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: wn 0.5 rad/s, zeta 0.4, 2 %wn 2 rad/s, zeta 0.7, 5 %wn 0.1 rad/s, zeta 0.2, 2 %

Angular frequency in radians per second. If you have the natural frequency f_n in Hz, enter 2π f_n.

Results

Natural frequency in radians per second. The settling time is from the exponential envelope, slightly longer than the exact crossing.

Overshoot25.383%
Time to the first peak6.8555s
Settling time (envelope)19.996s
Rise time 0–100 %4.3258s
Damped frequency ω_d in rad/s0.458261/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: wn 0.5 rad/s, zeta 0.4, 2 %. The inputs, in the units selected above:

InputValue
Natural frequency ω_n in rad/s0.50000 1/s
Damping ratio0.40000 -
Settling band2.0000 %

Applying the formula below gives:

ResultValue
Overshoot25.383 %
Time to the first peak6.8555 s
Settling time (envelope)19.996 s
Rise time 0–100 %4.3258 s
Damped frequency ω_d in rad/s0.45826 1/s

Open this example in the calculator and change any input.

Formula

\(M_p = e^{-\zeta\pi/\sqrt{1-\zeta^2}}, \quad t_p = \frac{\pi}{\omega_d}, \quad t_s = \frac{-\ln(\epsilon\sqrt{1-\zeta^2})}{\zeta\omega_n}, \quad \omega_d = \omega_n\sqrt{1-\zeta^2}, \quad t_r = \frac{\pi - \arccos\zeta}{\omega_d}\)

Variables

Symbol Meaning SI unit
\(\omega_n\) Natural (angular) frequency rad/s
\(\zeta\) Damping ratio -
\(\epsilon\) Settling band -
\(M_p\) Overshoot -
\(t_p\) Time to the first peak s
\(t_s\) Settling time (envelope) s
\(t_r\) Rise time 0–100 % s
\(\omega_d\) Damped (angular) frequency rad/s

Method and standards

Analytic step response.

Where it is used

  • Loop performance specification.
  • Control examinations.

Common mistakes

  • Hz instead of rad/s.
  • Applying to non-second-order loops.

Assumptions and limits

  • Underdamped, no zeros.
  • ω_n and ω_d are angular frequencies in rad/s (shown as 1/s); a natural frequency in Hz must be multiplied by 2π first.

References

  • Standard second-order response (Ogata, Modern Control Engineering, ch. 5)

Questions and answers

What overshoot does ζ = 0.4 give?

25.4 %.

How long to settle within 2 % with ω_n = 0.5 rad/s?

20.0 s by the envelope (about 4/(ζω_n) = 20 s).

What damping is usual for loops?

0.4 to 0.7; quarter decay corresponds to about 0.22.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.