Worked example
Example: K_u 4, P_u 60 s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Ultimate gain | 4.0000 - |
| Ultimate period | 60.000 s |
Applying the formula below gives:
| Result | Value |
|---|---|
| PI gain | 1.2500 |
| PI integral time | 132.00 s |
| PID gain | 1.8182 |
| PID integral time | 132.00 s |
| PID derivative time | 9.5238 s |
Open this example in the calculator and change any input.
Formula
\(K_c = \frac{K_u}{3.2},\ T_i = 2.2P_u\ \text{(PI)}; \quad K_c = \frac{K_u}{2.2},\ T_i = 2.2P_u,\ T_d = \frac{P_u}{6.3}\ \text{(PID)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(K_u\) | Ultimate gain | - |
| \(P_u\) | Ultimate period | s |
| \(K_{c,PI}\) | PI gain | - |
| \(T_{i,PI}\) | PI integral time | s |
| \(K_{c,PID}\) | PID gain | - |
| \(T_{i,PID}\) | PID integral time | s |
| \(T_{d,PID}\) | PID derivative time | s |
Method and standards
Tyreus–Luyben rules.
Where it is used
- Temperature, level and pressure loops.
- After a relay auto-tune.
Common mistakes
- Applying ideal-form settings to a series controller.
- Testing at an unrepresentative load.
Assumptions and limits
- Self-regulating loops.
References
- Tyreus and Luyben (1992)
- Ind. Eng. Chem. Res. 31: 2625; Seborg
- Edgar
- Mellichamp and Doyle
- Process Dynamics and Control
- 4th ed. (Wiley, 2016)
- ch. 12
Questions and answers
How do I get K_u and P_u?
From a relay (auto-tune) test, or by raising P-only gain until the loop oscillates steadily.
Why not Ziegler–Nichols?
Z–N gives quarter-amplitude decay, too aggressive for most process loops.
What do the defaults represent?
An ultimate gain of 4 and a 60 s ultimate period.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.