Worked example
Example: Closed tank, wet leg: span 2 m, zero 0.3 m, leg 2.5 m, water 1000 / 1000. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Level span to measure | 2.0000 m |
| Lowest level to measure, above the lower (high-side) tap | 0.30000 m |
| Low-side connection | Wet (filled) reference leg |
| Wet leg height above the lower tap | 2.5000 m |
| Process liquid density | 1,000.0 kg/m³ |
| Wet leg fill density | 1,000.0 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Lower range value | -2,200.0 mmWC |
| Upper range value | -200.00 mmWC |
| Calibrated span | 2,000.0 mmWC |
Open this example in the calculator and change any input.
Formula
\(LRV = \rho_p g h_0 - \rho_l g H \qquad URV = \rho_p g (h_0 + h_s) - \rho_l g H \qquad \Delta p_s = URV - LRV\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(h_s\) | level span | m |
| \(h_0\) | lowest level above lower tap | m |
| \(\text{leg}\) | dry/open or wet leg | – |
| \(H\) | wet leg height | m |
| \(\rho_p\) | process density | kg/m³ |
| \(\rho_l\) | leg fill density | kg/m³ |
| \(LRV\) | lower range value | Pa |
| \(URV\) | upper range value | Pa |
| \(\Delta p_s\) | span | Pa |
| \(g\) | standard gravity | m/s² |
Method and standards
Hydrostatic heads of the process and reference legs; the high side connected to the lower tap.
Where it is used
- Calibrating level transmitters on tanks and vessels.
- Choosing between dry and wet legs.
- Commissioning checks.
Common mistakes
- Using water density for other liquids.
- Forgetting the transmitter's mounting height below the tap.
- Leaving a wet leg partly empty.
Assumptions and limits
- Constant densities; legs fully filled or empty as chosen.
- The vapour or gas density above the liquid is neglected. For boiler drums, where steam density matters, use the drum level DP compensation calculator.
References
- Hydrostatics of the process and reference legs
Questions and answers
How do I range a DP level transmitter with a wet leg?
For water level from 0.3 m to 2.3 m above the lower tap with a 2.5 m water-filled wet leg, LRV is −2200 mmWC and URV −200 mmWC: a 2000 mmWC span below zero.
Why are the values negative?
The wet leg's head on the low side is larger than the process head; this zero elevation is normal.
Open tank?
With the low side vented, LRV and URV are just the process heads at the two levels.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.