Worked example
Example: 2 m tank, 0.8 m cone, 3 m shell; level 2 m; 5 m³ wanted. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Tank inside diameter | 2.0000 m |
| Height of the cone | 0.80000 m |
| Height of the cylindrical part | 3.0000 m |
| Level above the cone apex | 2.0000 m |
| Volume wanted (to find its level) | 5.0000 m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Volume at the level | 4.6077 m³ |
| Total volume | 10.263 m³ |
| Volume of the cone | 0.83776 m³ |
| Level for the volume wanted | 2.1249 m |
| Share of the total volume | 44.898 % |
Open this example in the calculator and change any input.
Formula
\(V(L) = V_c \left(\frac{L}{h_c}\right)^3\ (L \le h_c), \quad V(L) = V_c + \frac{\pi D^2}{4}(L - h_c), \quad V_c = \frac{\pi D^2 h_c}{12}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D\) | Tank inside diameter | m |
| \(h_c\) | Height of the cone | m |
| \(H_s\) | Height of the cylindrical part | m |
| \(L\) | Level above the cone apex | m |
| \(V_t\) | Volume wanted (to find its level) | m³ |
| \(V\) | Volume at the level | m³ |
| \(V_{tot}\) | Total volume | m³ |
| \(V_c\) | Volume of the cone | m³ |
| \(L_V\) | Level for the volume wanted | m |
| \(V/V_{tot}\) | Share of the total volume | - |
Method and standards
Similar cones and a cylinder.
Where it is used
- Level to volume in DCS.
- Hopper and process tank inventory.
Common mistakes
- Measuring level from the outlet instead of the apex.
- Truncated cones (a flat outlet).
Assumptions and limits
- Sharp apex, vertical tank.
- A volume wanted above the total volume hides only its level; the other results are still shown.
References
- Volume of a cone (similar cones scale with the cube of height) and a cylinder
Questions and answers
What does a 2 m tank with a 0.8 m cone and 3 m shell hold?
10.26 m³; the cone alone 0.838 m³.
Why is the bottom so non-linear?
Volume in the cone grows with the cube of the level.
Is the level from the apex?
Yes; add the nozzle offset if the transmitter zero is higher.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.