Worked example
Example: 12.5 t gross, 2.5 t tare, water, 2.5 m, 3 cells of 10 t. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Gross weight from the load cells | 12,500 kg |
| Empty tank weight (tare) | 2,500.0 kg |
| Liquid density | 1,000.0 kg/m³ |
| Tank inside diameter | 2.5000 m |
| Number of load cells | 3.0000 - |
| Rated capacity of each cell | 10,000 kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Net liquid mass | 10,000 kg |
| Liquid volume | 10.000 m³ |
| Level (vertical cylinder, flat bottom) | 2.0372 m |
| Load on each cell (even share) | 4,166.7 kg |
| Share of cell capacity used | 41.667 % |
Open this example in the calculator and change any input.
Formula
\(m = m_g - m_t, \quad V = \frac{m}{\rho}, \quad L = \frac{V}{\pi D^2/4}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(m_g\) | Gross weight from the load cells | kg |
| \(m_t\) | Empty tank weight (tare) | kg |
| \(\rho\) | Liquid density | kg/m³ |
| \(D\) | Tank inside diameter | m |
| \(n\) | Number of load cells | - |
| \(m_{cell}\) | Rated capacity of each cell | kg |
| \(m\) | Net liquid mass | kg |
| \(V\) | Liquid volume | m³ |
| \(L\) | Level (vertical cylinder, flat bottom) | m |
| \(m_1\) | Load on each cell (even share) | kg |
| \(u\) | Share of cell capacity used | - |
Method and standards
Mass balance.
Where it is used
- Batching and inventory.
- Silo and reactor weighing.
Common mistakes
- Rigid pipe connections.
- Uneven load sharing.
Assumptions and limits
Even sharing between cells; the page warns when the share of rated capacity passes 100 %. Wind, seismic load, shock and uneven sharing need further margin, set by the cell maker's guidance.
Flat-bottom vertical tank.
References
- Mass balance; level from volume of a vertical cylinder
Questions and answers
12.5 t gross, 2.5 t tare, water, 2.5 m diameter?
10 t net, 10 m³, level 2.04 m.
How much margin on cells?
Load cells are usually used to well under their rated capacity to allow for wind, shock and uneven sharing.
Why weigh instead of level?
Mass is what is usually wanted, and foam or density change does not affect it.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.