Worked example
Example: 50 m² tank, transmitters 2 m apart. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Bottom transmitter (absolute or gauge, same basis) | 1.8500 bar |
| Middle transmitter | 1.6900 bar |
| Top (vapour space) transmitter | 1.0000 bar |
| Vertical distance bottom to middle transmitter | 2.0000 m |
| Tank cross-section area | 50.000 m² |
| Bottom transmitter height above tank floor | 0.20000 m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Liquid density | 815.77 kg/m³ |
| Liquid mass above the bottom transmitter | 433.38 t |
| Liquid level above tank floor | 10.825 m |
| Liquid volume above the bottom transmitter | 531.25 m³ |
Open this example in the calculator and change any input.
Formula
\(\rho = \frac{p_b - p_m}{gh_{bm}}, \quad M = \frac{A(p_b - p_t)}{g}, \quad L = \frac{p_b - p_t}{\rho g} + z_b\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p_b\) | Bottom transmitter (absolute or gauge, same basis) | Pa |
| \(p_m\) | Middle transmitter | Pa |
| \(p_t\) | Top (vapour space) transmitter | Pa |
| \(h_{bm}\) | Vertical distance bottom to middle transmitter | m |
| \(A\) | Tank cross-section area | m² |
| \(z_b\) | Bottom transmitter height above tank floor | m |
| \(\rho\) | Liquid density | kg/m³ |
| \(M\) | Liquid mass above the bottom transmitter | kg |
| \(L\) | Liquid level above tank floor | m |
| \(V\) | Liquid volume above the bottom transmitter | m³ |
Method and standards
Hydrostatics.
Where it is used
- Ethanol, molasses and fuel tank inventory.
- Custody transfer support.
Common mistakes
- Middle transmitter uncovered.
- Mixing gauge and absolute transmitters.
Assumptions and limits
- Uniform density; vertical-wall tank; the middle transmitter covered by liquid (otherwise the page reports failure).
- Standard gravity; custody-transfer HTG (API MPMS 3.6) uses local gravity, which changes the mass by up to about 0.3 %.
References
- Hydrostatic tank gauging (Lipták, Instrument Engineers' Handbook, 4th ed. (CRC Press), vol. 1; API MPMS ch. 3.6 principle)
Questions and answers
Why measure mass by pressure?
The bottom pressure is the weight of the liquid column per unit area: mass = AΔp/g, whatever the temperature or density.
What does the middle transmitter add?
Density, from the pressure difference over a known height, and from that level and volume.
What do the defaults represent?
A 50 m² tank with transmitters 2 m apart.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.