Worked example
Example: Illustrative 415 V bridge at 30 degrees. The inputs, in the units selected above:
| Input | Value |
|---|---|
| AC line-to-line voltage (RMS) | 415.00 V |
| Supply frequency | 50.000 Hz |
| Firing (delay) angle | 30.000 ° |
| DC current | 200.00 A |
| Commutating inductance per phase | 0.10000 mH |
Applying the formula below gives:
| Result | Value |
|---|---|
| Ideal no-load DC voltage at α = 0 | 560.45 V |
| DC output voltage | 479.36 V |
| Commutation overlap angle | 2.3694 ° |
| DC power | 95.872 kW |
| Displacement factor | 0.85532 |
| Fundamental AC line current | 155.94 A |
Open this example in the calculator and change any input.
Formula
\(V_d = \frac{3\sqrt2}{\pi}V_{LL}\cos\alpha - \frac{3\omega L_c}{\pi}I_d, \quad \cos(\alpha + \mu) = \cos\alpha - \frac{2\omega L_cI_d}{\sqrt2V_{LL}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_{LL}\) | AC line-to-line voltage (RMS) | V |
| \(f\) | Supply frequency | 1/s |
| \(\alpha\) | Firing (delay) angle | rad |
| \(I_d\) | DC current | A |
| \(L_c\) | Commutating inductance per phase | H |
| \(V_{d0}\) | Ideal no-load DC voltage at α = 0 | V |
| \(V_d\) | DC output voltage | V |
| \(\mu\) | Commutation overlap angle | rad |
| \(P_d\) | DC power | W |
| \(\cos\varphi_1\) | Displacement factor | - |
| \(I_1\) | Fundamental AC line current | A |
Method and standards
Thyristor bridge.
Where it is used
- DC drives, electrolysers and battery chargers.
- Estimating reactive power of phase-controlled loads.
Common mistakes
- Using line-to-neutral voltage in 1.35 V_LL.
- Ignoring overlap at high current.
Assumptions and limits
- Smooth (continuous) DC current; balanced sinusoidal supply; ideal thyristors.
References
- Three-phase fully controlled bridge with commutation overlap
Questions and answers
Why does the power factor fall with firing angle?
The fundamental current shifts by about α behind the voltage, so the drive draws reactive power at low speed.
What limits inversion?
The overlap plus the thyristor turn-off margin must fit before 180°, or commutation fails.
What do the defaults represent?
An illustrative 415 V, 50 Hz bridge fired at 30° carrying 200 A with 0.1 mH commutating inductance.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Mohan, Undeland and Robbins, Power Electronics: Converters, Applications and Design, 3rd ed. (Wiley, 2003)