Characteristic Harmonics of a p-Pulse Converter

Characteristic harmonic orders kp ± 1 of an ideal p-pulse rectifier, the first two harmonic currents by the 1/h rule and current THD up to a chosen order.

Thermal power plantProcess steam and utilitiesChemical and fertiliser

Inputs

Examples: Illustrative 6-pulse, 500 A, to 49th12-pulse, 1000 A, to 49th18-pulse to 99th

Accepted: 0.1 to 100,000 A
Accepted: 5 to 100

Results

Ideal rectangular line current: only orders h = kp ± 1 appear, with I_h = I₁/h. Real converters with commutation overlap have lower high-order harmonics; drives with no DC choke draw much more 5th and 7th (THD 80–120 %). Twelve-pulse cancellation needs equal loading and phase-shifted transformer windings.

Lowest characteristic order5.0000
Current at the lowest order100.00A
Current at the next order71.429A
Current THD (ideal)30.015%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 6-pulse, 500 A, to 49th. The inputs, in the units selected above:

InputValue
Pulse number6-pulse
Fundamental current500.00 A
Highest order counted49.000 -

Applying the formula below gives:

ResultValue
Lowest characteristic order5.0000
Current at the lowest order100.00 A
Current at the next order71.429 A
Current THD (ideal)30.015 %

Open this example in the calculator and change any input.

Formula

\(h = kp \pm 1, \quad I_h = \frac{I_1}{h}, \quad THD_I = \sqrt{\sum_h\frac{1}{h^2}}\)

Variables

Symbol Meaning SI unit
\(p\) Pulse number -
\(I_1\) Fundamental current A
\(h_{max}\) Highest order counted -
\(h_1\) Lowest characteristic order -
\(I_{h_1}\) Current at the lowest order A
\(I_{h_1 + 2}\) Current at the next order A
\(THD_I\) Current THD (ideal) -

Method and standards

Converter harmonics.

Where it is used

  • Early harmonic studies of rectifiers and drives.
  • Choosing pulse number for large drives.

Common mistakes

  • Expecting 12-pulse cancellation with unbalanced bridges.
  • Applying ideal spectra to choke-less drives.

Assumptions and limits

  • Ideal commutation; constant DC current; balanced supply.

References

  • Characteristic harmonics of ideal converters

Questions and answers

Why does a 12-pulse converter cancel the 5th and 7th?

Two 6-pulse bridges fed 30° apart produce 5th and 7th currents in opposite phase on the primary side.

Is the 1/h rule realistic?

It is an upper envelope for a well-smoothed DC current; overlap reduces high orders, a missing DC choke raises low orders.

What do the defaults represent?

An illustrative 6-pulse converter drawing 500 A fundamental, harmonics counted to the 49th.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Arrillaga and Watson, Power System Harmonics, 2nd ed. (Wiley, 2003)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.