Worked example
Example: Illustrative 300 kvar 4.7 filter on 415 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Bus line voltage | 415.00 V |
| Bus short-circuit power | 20.000 MVA |
| Filter effective kvar at fundamental | 300.00 kvar |
| Tuning order | 4.7000 - |
| Filter quality factor | 40.000 - |
| Harmonic order of the source current | 5.0000 - |
| Harmonic current from the load | 120.00 A |
Applying the formula below gives:
| Result | Value |
|---|---|
| Capacitor reactance at fundamental | 0.60130 Ω |
| Reactor reactance at fundamental | 0.027221 Ω |
| Filter resistance | 0.003198 Ω |
| Harmonic current into the filter | 87.594 A |
| Harmonic current into the supply | 32.880 A |
| Harmonic voltage at the bus | 0.59086 % |
Open this example in the calculator and change any input.
Formula
\(X_C = \frac{V^2}{Q_{eff}}\frac{h_t^2}{h_t^2 - 1}, \quad X_L = \frac{X_C}{h_t^2}, \quad R = \frac{h_tX_L}{Q_f}, \quad I_{f,h} = I_h\frac{Z_s(h)}{Z_s(h) + Z_f(h)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Bus line voltage | V |
| \(S_{sc}\) | Bus short-circuit power | VA |
| \(Q_{eff}\) | Filter effective kvar at fundamental | var |
| \(h_t\) | Tuning order | - |
| \(Q_f\) | Filter quality factor | - |
| \(h\) | Harmonic order of the source current | - |
| \(I_h\) | Harmonic current from the load | A |
| \(X_C\) | Capacitor reactance at fundamental | Ω |
| \(X_L\) | Reactor reactance at fundamental | Ω |
| \(R\) | Filter resistance | Ω |
| \(I_{f,h}\) | Harmonic current into the filter | A |
| \(I_{s,h}\) | Harmonic current into the supply | A |
| \(V_h\) | Harmonic voltage at the bus | - |
Method and standards
Filter design.
Where it is used
- Harmonic mitigation for drives and rectifiers.
- Checking filter overloading from other loads' harmonics.
Common mistakes
- Ignoring harmonics imported from the supply.
- Rating the capacitor at bus voltage.
Assumptions and limits
- Inductive source at harmonics; one dominant harmonic.
References
- Single-tuned filter design and current division
Questions and answers
Why tune to 4.7 rather than 5?
Capacitance falls with age and temperature, raising the tuned frequency; starting below the 5th keeps it from sitting exactly on the harmonic.
What quality factor is typical?
About 20–100 for reactors in single-tuned filters; lower Q widens the band but adds losses.
What do the defaults represent?
An illustrative 300 kvar filter tuned to 4.7 with Q 40 on a 415 V bus of 20 MVA fault level, absorbing a 120 A 5th harmonic.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Dugan, McGranaghan, Santoso and Beaty, Electrical Power Systems Quality, 3rd ed. (McGraw-Hill, 2012)