FireCADCalc

Voltage Sag Magnitude versus Fault Distance (Divider Model)

Remaining voltage at a common bus during a three-phase fault on a radial feeder, from source fault level and feeder impedance, and the critical distance for a sag.

Thermal power plantProcess steam and utilitiesChemical and fertiliser

Inputs

Examples: Illustrative 11 kV, fault 5 km out33 kV line, 20 km, 50 % threshold415 V cable fault at 100 m

Accepted: 0.1 to 800 kV
Accepted: 0.1 to 100,000 MVA
Accepted: 0.01 to 10 Ω/km
Accepted: 0 to 200 km
Accepted: 5 to 95 %

Results

Voltage divider: V_sag = Z_f/(Z_s + Z_f) with Z_s = V²/S_sc and Z_f = z·L (same impedance angle assumed). Faults closer than L_crit drive the bus below V_t; counting faults per km-year inside it estimates how often sensitive loads trip. Single-phase faults and transformer winding connections change what the load sees.

Source impedance0.48400Ω
Feeder impedance to the fault2.0000Ω
Voltage at the common bus during the fault80.515%
Critical distance for the threshold2.8233km

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 11 kV, fault 5 km out. The inputs, in the units selected above:

InputValue
Nominal line voltage11.000 kV
Fault level at the common bus250.00 MVA
Feeder impedance magnitude0.40000 Ω/km
Distance to fault5.0000 km
Sag threshold of interest70.000 %

Applying the formula below gives:

ResultValue
Source impedance0.48400 Ω
Feeder impedance to the fault2.0000 Ω
Voltage at the common bus during the fault80.515 %
Critical distance for the threshold2.8233 km

Open this example in the calculator and change any input.

Formula

\(V_{sag} = \frac{Z_f}{Z_s + Z_f}, \quad Z_s = \frac{V^2}{S_{sc}}, \quad L_{crit} = \frac{Z_s}{z}\frac{V_t}{1 - V_t}\)

Variables

Symbol Meaning SI unit
\(V\) Nominal line voltage V
\(S_{sc}\) Fault level at the common bus VA
\(z\) Feeder impedance magnitude Ω/m
\(L\) Distance to fault m
\(V_t\) Sag threshold of interest -
\(Z_s\) Source impedance Ω
\(Z_f\) Feeder impedance to the fault Ω
\(V_{sag}\) Voltage at the common bus during the fault -
\(L_{crit}\) Critical distance for the threshold m

Method and standards

Sag divider.

Where it is used

  • Process plant trip studies.
  • Choosing ride-through for drives and contactors.

Common mistakes

  • Mixing per-phase and line impedances.
  • Ignoring transformer phase shifts for unbalanced faults.

Assumptions and limits

  • Three-phase fault; radial feeder; equal impedance angles; pre-fault voltage 1 pu.

References

  • Voltage divider model of sags

Questions and answers

Why does a distant fault cause a sag?

Fault current flows through the source impedance, pulling down the common bus in proportion to how close the fault is.

How is the critical distance used?

Multiply the feeder length inside it by the fault rate per km-year to estimate how many sags below the threshold to expect.

What do the defaults represent?

An illustrative 11 kV bus with 250 MVA fault level, feeders of 0.4 Ω/km, a fault 5 km out and a 70 % threshold.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Bollen, Understanding Power Quality Problems: Voltage Sags and Interruptions (IEEE Press, 2000)

Related calculators