Worked example
Example: Illustrative 11 kV, fault 5 km out. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Nominal line voltage | 11.000 kV |
| Fault level at the common bus | 250.00 MVA |
| Feeder impedance magnitude | 0.40000 Ω/km |
| Distance to fault | 5.0000 km |
| Sag threshold of interest | 70.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Source impedance | 0.48400 Ω |
| Feeder impedance to the fault | 2.0000 Ω |
| Voltage at the common bus during the fault | 80.515 % |
| Critical distance for the threshold | 2.8233 km |
Open this example in the calculator and change any input.
Formula
\(V_{sag} = \frac{Z_f}{Z_s + Z_f}, \quad Z_s = \frac{V^2}{S_{sc}}, \quad L_{crit} = \frac{Z_s}{z}\frac{V_t}{1 - V_t}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Nominal line voltage | V |
| \(S_{sc}\) | Fault level at the common bus | VA |
| \(z\) | Feeder impedance magnitude | Ω/m |
| \(L\) | Distance to fault | m |
| \(V_t\) | Sag threshold of interest | - |
| \(Z_s\) | Source impedance | Ω |
| \(Z_f\) | Feeder impedance to the fault | Ω |
| \(V_{sag}\) | Voltage at the common bus during the fault | - |
| \(L_{crit}\) | Critical distance for the threshold | m |
Method and standards
Sag divider.
Where it is used
- Process plant trip studies.
- Choosing ride-through for drives and contactors.
Common mistakes
- Mixing per-phase and line impedances.
- Ignoring transformer phase shifts for unbalanced faults.
Assumptions and limits
- Three-phase fault; radial feeder; equal impedance angles; pre-fault voltage 1 pu.
References
- Voltage divider model of sags
Questions and answers
Why does a distant fault cause a sag?
Fault current flows through the source impedance, pulling down the common bus in proportion to how close the fault is.
How is the critical distance used?
Multiply the feeder length inside it by the fault rate per km-year to estimate how many sags below the threshold to expect.
What do the defaults represent?
An illustrative 11 kV bus with 250 MVA fault level, feeders of 0.4 Ω/km, a fault 5 km out and a 70 % threshold.