FireCADCalc

Hold-Up (Bulk) Capacitor for a Power Interruption

Capacitance needed to keep a load running for a hold-up time after the supply drops, from the load power, efficiency and the starting and minimum capacitor voltages.

Inputs

Examples: Illustrative: 60 W, 20 ms, 380 V bus down to 300 V, 90 %12 V controller ride-through: 5 W, 50 ms, 12 V to 8 VServer supply 500 W, 10 ms, 390 V to 330 V

Accepted: 0.001 to 1,000,000 W
Accepted: 0.01 to 100,000 ms
Accepted: 1 to 1,000 V
Accepted: 0.5 to 1,000 V
Accepted: 30 to 100 %

Results

Energy balance ½C(V₁² − V₂²) = Pt/η. Add margin for capacitor tolerance (−20 %) and ageing, and check the capacitor's ripple current rating.

Required capacitance49.020µF
Energy delivered by the capacitor1.3333J
Fraction of the stored energy used37.673%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative: 60 W, 20 ms, 380 V bus down to 300 V, 90 %. The inputs, in the units selected above:

InputValue
Load power60.000 W
Hold-up time20.000 ms
Capacitor voltage at the start380.00 V
Minimum voltage the converter accepts300.00 V
Converter efficiency90.000 %

Applying the formula below gives:

ResultValue
Required capacitance49.020 µF
Energy delivered by the capacitor1.3333 J
Fraction of the stored energy used37.673 %

Open this example in the calculator and change any input.

Formula

\(C = \frac{2Pt_h}{\eta(V_1^2 - V_2^2)}\)

Variables

Symbol Meaning SI unit
\(P\) Load power W
\(t_h\) Hold-up time s
\(V_1\) Capacitor voltage at the start V
\(V_2\) Minimum voltage the converter accepts V
\(\eta\) Converter efficiency -
\(C\) Required capacitance F
\(\Delta E\) Energy delivered by the capacitor J
\(1 - (V_2/V_1)^2\) Fraction of the stored energy used -

Method and standards

Energy balance of a discharging capacitor.

Where it is used

  • Offline power supplies and LED drivers.
  • Ride-through for controllers, memories and data loggers.

Common mistakes

  • Using V₁²/2 without subtracting the minimum voltage.
  • Ignoring capacitor tolerance and ageing.

Assumptions and limits

  • Constant-power load, ideal capacitor.

References

  • Capacitor energy balance for hold-up

Questions and answers

Why does the minimum voltage matter so much?

The usable energy is ½C(V₁² − V₂²); letting the converter run down to a lower voltage releases much more of the stored energy.

What hold-up time is typical?

Mains-powered IT supplies often specify 10–20 ms, one full mains cycle, to ride through brief dips and transfer switching.

What do the defaults represent?

An illustrative 60 W supply with a 380 V PFC bus that must ride through 20 ms down to 300 V at 90 % efficiency.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Erickson and Maksimović, Fundamentals of Power Electronics, 2nd ed. (Kluwer, 2001), ch. 18

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.