Worked example
Example: 200 residents at 135 L/day, one day. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Number of people (or equivalent users) | 200.00 - |
| Demand per person per day | 135.00 L |
| Days of storage | 1.0000 - |
| Fire-fighting reserve | 0 m³ |
| Water depth in the tank | 2.5000 m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Daily demand | 27.000 m³ |
| Storage needed | 27.000 m³ |
| Plan area of the tank at that depth | 10.800 m² |
| Diameter of a round tank | 3.7082 m |
| Side of a square tank | 3.2863 m |
Open this example in the calculator and change any input.
Formula
\(V_d = N q, \quad V = V_d\, d + V_f\)
\(A = V / h, \quad D = \sqrt{4A/\pi}, \quad s = \sqrt{A}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(N\) | Number of people (or equivalent users) | - |
| \(q\) | Demand per person per day | m³ |
| \(d\) | Days of storage | - |
| \(V_f\) | Fire-fighting reserve | m³ |
| \(h\) | Water depth in the tank | m |
| \(V_d\) | Daily demand | m³ |
| \(V\) | Storage needed | m³ |
| \(A\) | Plan area of the tank at that depth | m² |
| \(D\) | Diameter of a round tank | m |
| \(s\) | Side of a square tank | m |
Method and standards
Daily demand is people times demand per head; storage is the days required plus any fire reserve. The plan area follows from the water depth.
Where it is used
- Sizing sumps and overhead tanks.
- Plant township and canteen water supply.
- Checking existing storage after a headcount rise.
Common mistakes
- Leaving out free board and dead storage.
- Using residential demand for offices.
- Forgetting the fire reserve must be protected.
Assumptions and limits
- Average demand; peak pumping sized separately.
References
- Per-capita demand method (demand per head from the local code or client)
Questions and answers
How big a tank for 200 residents at 135 L/day?
27 m³ for one day; at 2.5 m water depth that is 10.8 m², a 3.7 m round tank or 3.3 m square.
Where does the demand per head come from?
Your local building code or the client's brief; it varies widely with building type.
How is the fire reserve handled?
Added on top, and kept below the domestic outlet so it is never drawn for daily use.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.