Sewer and Drain Pipe Size by Manning (Full and Part Full)

Diameter of a circular sewer or drain to carry a flow running full by Manning's equation, and the depth and velocity at the design flow in the size you choose.

Inputs

Examples: 120 L/s at 1 in 250, 450 mmStorm drain 0.6 m3/s, 900 mmSize found, running full

Results

Check the velocity against your standard's self-cleansing minimum and the maximum.

Diameter running just full804.36mm
Full-bore capacity of the chosen pipe809.60L/s
Depth ratio at the design flow64.083%
Velocity at the design flow1.3933m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 120 L/s at 1 in 250, 450 mm. The inputs, in the units selected above:

InputValue
Design flow120.00 L/s
Manning roughness0.013000 -
Pipe slope0.40000 %
Chosen diameter (0 to use the size found)450.00 mm

Applying the formula below gives:

ResultValue
Diameter running just full386.27 mm
Full-bore capacity of the chosen pipe180.32 L/s
Depth ratio at the design flow59.630 %
Velocity at the design flow1.2133 m/s

Open this example in the calculator and change any input.

Formula

\(D_{full} = \left(\frac{4^{5/3} Q n}{\pi\sqrt{S}}\right)^{3/8}, \quad Q = \frac{1}{n} A R^{2/3} S^{1/2}\)

Variables

Symbol Meaning SI unit
\(Q\) Design flow m³/s
\(n\) Manning roughness -
\(S\) Pipe slope -
\(D_c\) Chosen diameter (0 to use the size found) m
\(D_{full}\) Diameter running just full m
\(Q_f\) Full-bore capacity of the chosen pipe m³/s
\(y/D\) Depth ratio at the design flow -
\(v\) Velocity at the design flow m/s

Method and standards

Manning.

Where it is used

  • Plant drains and sewers.
  • Storm water pipes.

Common mistakes

  • n from the wrong material.
  • Designing to the 0.94 D peak.

Assumptions and limits

  • Uniform steady flow.
  • The calculator does not pick a standard size: enter the next available size above D_full as the chosen diameter to get its capacity, depth and velocity.

References

  • Manning's equation for circular conduits
  • full and part full

Questions and answers

120 L/s at 1 in 250, n 0.013?

About 390 mm running full; a 450 mm pipe runs about 60 % deep at 1.2 m/s.

Why design part full?

Room for peaks and ventilation; many standards limit depth.

Self-cleansing?

Keep the velocity above your standard's minimum, often 0.6 to 0.8 m/s.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.