Storm Water Runoff by the Rational Method

Peak storm water runoff from a catchment by the rational method Q = C i A, and the runoff volume over the storm, for drain and sump sizing.

Inputs

Examples: Paved yard 2 ha, C 0.85, 50 mm/h, 1 hRoof 5 000 m², C 0.95, 100 mm/h, 15 minPlant site 10 ha mixed, C 0.6, 75 mm/h, 30 min

Share of rain that runs off: high for roofs and paving, low for lawns and open ground.

Results

The rational method suits small catchments; use the intensity for a duration equal to the time of concentration, from local rainfall data.

Peak runoff1.2500m³/s
Runoff volume over the storm2,250.0m³

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Paved yard 2 ha, C 0.85, 50 mm/h, 1 h. The inputs, in the units selected above:

InputValue
Runoff coefficient85.000 %
Rainfall intensity for the design storm50.000 mm/h
Catchment area2.0000 ha
Storm duration1.0000 h

Applying the formula below gives:

ResultValue
Peak runoff0.23611 m³/s
Runoff volume over the storm850.00 m³

Open this example in the calculator and change any input.

Formula

\(Q = C\, i\, A\)

\(V = Q\, t\)

Variables

Symbol Meaning SI unit
\(C\) runoff coefficient -
\(i\) rainfall intensity m/s
\(A\) catchment area m²
\(t\) storm duration s
\(Q\) peak runoff m³/s
\(V\) runoff volume m³

Method and standards

The rational method takes peak runoff as the share C of rainfall intensity falling on the catchment area. In SI units with i in m/s and A in m², Q comes out in m³/s.

Where it is used

  • Sizing plant storm drains, sumps and pumps.
  • Checking coal yard and ash pond runoff.
  • Planning rainwater harvesting.

Common mistakes

  • Mixing units (mm/h with hectares needs conversion).
  • Using a 24-hour average intensity for a short time of concentration.
  • Applying it to large catchments.

Assumptions and limits

  • Small catchments; uniform rain over the area.
  • The volume V = Q t holds the peak rate for the whole storm. For the volume, enter the intensity for a storm of duration t (from the IDF data); using the time-of-concentration intensity with a longer duration overstates the volume.

References

  • Rational method

Questions and answers

What runoff comes from 2 ha of paving in a 50 mm/h storm?

About 0.24 m³/s with C 0.85, and 850 m³ over one hour.

What runoff coefficient should I use?

Near 1 for roofs and paving, much lower for lawns and open ground; use local guidance for the surfaces.

Which rainfall intensity?

The intensity for a storm lasting the catchment's time of concentration at the chosen return period, from local rainfall data.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.