FireCADCalc

Flash Point Estimate from Vapour Pressure (Leslie–Geniesse)

Closed-cup flash point estimate of an organic liquid: the temperature where its vapour pressure equals 1 atm/(8β), with β from its C, H, O, S and halogen atoms.

Distillery and ethanolRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: Phenol (Perry's example: 350.84 K)Ethanol (DIPPR-form constants)

Results

Perry's: about 4 K. Measured closed-cup values (ASTM D 56, D 93) govern classification. Screening estimate only, not a safety study or a basis for protective design.

The vapour-pressure equation is used as entered; make sure the flash point lies inside the temperature range it was fitted for.

Moles of O₂ per mole of fuel3.0000
Vapour pressure at the flash point4.2219kPa
Flash point14.558°C
Stoichiometric vapour concentration in air6.5278%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Phenol (Perry's example: 350.84 K). The inputs, in the units selected above:

InputValue
Carbon atoms6.0000 -
Hydrogen atoms6.0000 -
Oxygen atoms1.0000 -
Sulfur and silicon atoms0 -
Halogen atoms0 -
Vapour pressure A (ln p/Pa = A + B/T + C ln T + D T^E)95.444 -
B (K)-10,113 -
C-10.090 -
D6.7603e-18 -
E6.0000 -

Applying the formula below gives:

ResultValue
Moles of O₂ per mole of fuel7.0000
Vapour pressure at the flash point1.8094 kPa
Flash point77.689 °C
Stoichiometric vapour concentration in air2.9060 %

Open this example in the calculator and change any input.

Formula

\(p^*(T_{FP}) = \frac{1\ \mathrm{atm}}{8\beta}, \quad \beta = N_C + N_{Si} + N_S + \frac{N_H - N_X - 2N_O}{4}, \quad C_{st} = \frac{1}{1 + 4.773\beta}\)

Variables

Symbol Meaning SI unit
\(N_C\) Carbon atoms -
\(N_H\) Hydrogen atoms -
\(N_O\) Oxygen atoms -
\(N_S + N_{Si}\) Sulfur and silicon atoms -
\(N_X\) Halogen atoms -
\(A\) Vapour pressure A (ln p/Pa = A + B/T + C ln T + D T^E) -
\(B\) B (K) -
\(C\) C -
\(D\) D -
\(E\) E -
\(\beta\) Moles of O₂ per mole of fuel -
\(p^*\) Vapour pressure at the flash point Pa
\(T_{FP}\) Flash point K
\(C_{st}\) Stoichiometric vapour concentration in air -

Method and standards

Leslie–Geniesse with the user's vapour-pressure equation.

Where it is used

  • Screening solvent hazards.
  • Checking supplier flash points.

Common mistakes

  • Using open-cup data for comparison.
  • A vapour-pressure equation fitted far from the flash point.

Assumptions and limits

  • Organic compounds; closed cup.
  • The vapour-pressure equation's own temperature range is not an input, so the result is not checked against it: confirm the flash point lies inside it.

References

  • Perry's Chemical Engineers' Handbook
  • 9th ed. (McGraw-Hill, 2019)
  • sec. 2
  • Eqs. (2-122)
  • (2-123) and (2-128) (Leslie and Geniesse, International Critical Tables) with the phenol example

Questions and answers

What does Perry's example give?

Phenol (β = 7): 350.84 K, 0.4 % below the DIPPR value of 352.15 K.

Why 1/(8β)?

At the flash point the vapour is roughly at the lower flammability limit, which for many organics is about half the stoichiometric concentration; Leslie and Geniesse put it at 1/(8β) atm.

What vapour-pressure equation is used?

ln p = A + B/T + C ln T + D Tᴱ (the DIPPR form, p in Pa). For Antoine constants set C = D = 0 and adjust.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.