Worked example
Example: 10 m³, air to 6 % O2, 1 to 5 bar(a). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Vessel volume | 10.000 m³ |
| Initial oxygen | 21.000 % |
| Target oxygen | 6.0000 % |
| Low pressure of the cycle (absolute) | 1.0132 bar |
| High pressure of the cycle (absolute) | 5.0000 bar |
| Temperature | 25.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pressure cycles needed | 1.0000 |
| Oxygen after those cycles | 4.2556 % |
| Nitrogen for the pressure purge | 45.053 kg |
| Nitrogen volume for a sweep purge (at vessel conditions) | 12.528 m³ |
Open this example in the calculator and change any input.
Formula
\(y_j = y_0\left(\frac{p_L}{p_H}\right)^j, \quad m_{N_2} = j\frac{(p_H - p_L)V}{RT}M_{N_2}, \quad Qt = V\ln\frac{y_0}{y_t}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Vessel volume | m³ |
| \(y_0\) | Initial oxygen | - |
| \(y_t\) | Target oxygen | - |
| \(p_L\) | Low pressure of the cycle (absolute) | Pa |
| \(p_H\) | High pressure of the cycle (absolute) | Pa |
| \(T\) | Temperature | K |
| \(j\) | Pressure cycles needed | - |
| \(y_j\) | Oxygen after those cycles | - |
| \(m_{N_2}\) | Nitrogen for the pressure purge | kg |
| \(Q t\) | Nitrogen volume for a sweep purge (at vessel conditions) | m³ |
Method and standards
Ideal-mixing purge relations.
Where it is used
- Start-up and shutdown inerting procedures.
Common mistakes
- Ignoring dead legs.
- Using gauge pressures.
Assumptions and limits
- Ideal gas; perfect mixing; pure nitrogen. Impure nitrogen (99 % or PSA 97 %) carries its own oxygen, which sets a floor on the oxygen reached; more cycles are then needed, or the target cannot be met.
References
- Purging by ideal mixing (definitions; see Perry's sec. 23 on inerting)
Questions and answers
Why does each cycle multiply by p_L/p_H?
Pressurising with pure nitrogen dilutes the oxygen by that ratio; venting back keeps the same fraction.
Which uses less nitrogen?
Pressure purging with a large pressure ratio usually does, for vessels that can take the pressure.
Why ln(y₀/y) volumes for a sweep?
With perfect mixing the oxygen falls exponentially with the volumes swept through.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.