Worked example
Example: Methane, LFL 5 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Lower flammability limit | 5.0000 % |
| Carbon atoms in the fuel | 1.0000 - |
| Hydrogen atoms | 4.0000 - |
| Oxygen atoms | 0 - |
| Safety margin below LOC (percentage points) | 2.0000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Moles of O₂ per mole of fuel | 2.0000 |
| Limiting oxygen concentration | 10.000 % |
| Maximum O₂ to operate at | 8.0000 % |
Open this example in the calculator and change any input.
Formula
\(z = m + \frac{x}{4} - \frac{y}{2}\ (C_mH_xO_y), \quad LOC = z\cdot LFL\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(LFL\) | Lower flammability limit | - |
| \(m\) | Carbon atoms in the fuel | - |
| \(x\) | Hydrogen atoms | - |
| \(y\) | Oxygen atoms | - |
| \(\Delta\) | Safety margin below LOC (percentage points) | - |
| \(z\) | Moles of O₂ per mole of fuel | - |
| \(LOC\) | Limiting oxygen concentration | - |
| \(O_{2,max}\) | Maximum O₂ to operate at | - |
Method and standards
Perry's Eq. (23-8).
Where it is used
- Inerting design screening.
Common mistakes
- Using it instead of measured LOC.
- No margin for analyser error.
Assumptions and limits
- Approximate; measured data (ASTM E2079) govern. The estimate can be non-conservative for some fuels whose measured LOC is lower than z·LFL.
- Only C, H and O atoms are handled; fuels with N, S or halogens need measured values.
- The operating target subtracts a fixed margin in percentage points; inerting standards may set it as a percentage of the LOC depending on monitoring.
References
- Perry's Chemical Engineers' Handbook
- 9th ed. (McGraw-Hill, 2019)
- sec. 23
- Eq. (23-8): LOC = z·LFL
Questions and answers
What is LOC?
The oxygen concentration below which no mixture of the fuel with air and inert can burn.
Why z·LFL?
At the LFL the fuel just burns; the oxygen it uses there is z times the LFL.
What does methane give?
LFL 5 %, z = 2: LOC about 10 % O₂ (measured about 12 % with nitrogen).
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.