Worked example
Example: Toluene into a 100 pF drum, 60 s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Liquid velocity in the pipe | 3.0000 m/s |
| Pipe diameter | 50.000 mm |
| Pipe length | 10.000 m |
| Liquid relaxation time | 21.000 s |
| Filling time | 60.000 s |
| Capacitance of the isolated container | 100.00 pF |
| Minimum ignition energy of the vapour | 0.10000 mJ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Streaming current | 3.3024e-08 A |
| Charge accumulated | 1.9814e-06 C |
| Container voltage | 19,814 V |
| Spark energy available | 19.631 mJ |
| Spark energy over minimum ignition energy | 196.31 |
Open this example in the calculator and change any input.
Formula
\(I_s = 10\times10^{-6}(ud)^2\left[1 - \exp\left(-\frac{L}{u\tau}\right)\right], \quad Q = I_st, \quad V = \frac{Q}{C}, \quad J = \frac{Q^2}{2C}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(u\) | Liquid velocity in the pipe | m/s |
| \(d\) | Pipe diameter | m |
| \(L\) | Pipe length | m |
| \(\tau\) | Liquid relaxation time | s |
| \(t\) | Filling time | s |
| \(C\) | Capacitance of the isolated container | F |
| \(MIE\) | Minimum ignition energy of the vapour | J |
| \(I_s\) | Streaming current | A |
| \(Q\) | Charge accumulated | C |
| \(V\) | Container voltage | V |
| \(J\) | Spark energy available | J |
| \(J/MIE\) | Spark energy over minimum ignition energy | - |
Method and standards
Streaming current (u in m/s, d in m, I in A) and capacitor energy.
Where it is used
- Drum and tank filling with flammable solvents.
- Training on bonding and grounding.
Common mistakes
- Ignoring a person as a capacitor.
- Assuming conductive liquids are hazardous.
Assumptions and limits
- Isolated container; no charge leakage.
References
- Crowl and Louvar
- Chemical Process Safety: Fundamentals with Applications
- 2nd ed. (Prentice Hall, 2002)
- ch. 7
- eqs. 7-21 to 7-27 (streaming current, charge, capacitance, energy)
Questions and answers
Why does a slow fill help?
Streaming current grows with the square of velocity: halving the velocity cuts the charge rate to a quarter.
What capacitance does a drum have?
Roughly 100 pF for an isolated 200 L drum, about 200–300 pF for a person, and much more for large tanks.
What do the defaults represent?
Toluene (relaxation time 21 s) at 3 m/s through 10 m of 50 mm pipe into an isolated 100 pF drum for 60 s.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.