Worked example
Example: NPS 36 line, 12 miles, NPS 8 venturi plug. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Initial pressure (absolute) | 1,100.0 psi |
| Gas gravity (air = 1) | 0.58000 - |
| Pipeline inside diameter | 34.500 in |
| Length of the isolated section | 12.000 mi |
| Blowdown pipe inside diameter | 7.9810 in |
| Choke factor of the blowdown valve | Venturi lubricated plug (3.2) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Blowdown time | 331.70 min |
| Geometric volume of the section | 11,647 m³ |
Open this example in the calculator and change any input.
Formula
\(T = 0.0588\,\frac{P_1^{1/3}G^{1/2}D^2LF_c}{d^2}\ \ (\text{min; psia, in, mi})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_1\) | Initial pressure (absolute) | Pa |
| \(G\) | Gas gravity (air = 1) | - |
| \(D\) | Pipeline inside diameter | m |
| \(L\) | Length of the isolated section | m |
| \(d\) | Blowdown pipe inside diameter | m |
| \(F_c\) | Choke factor of the blowdown valve | - |
| \(T\) | Blowdown time | s |
| \(V\) | Geometric volume of the section | m³ |
Method and standards
AGA empirical blowdown formula.
Where it is used
- Sizing blowdown assemblies at mainline valves.
- Planning maintenance depressurisation.
Common mistakes
- Using gauge pressure.
- Using the nominal pipe size instead of the inside diameter.
Assumptions and limits
- Empirical; choked flow through the blowdown pipe for most of the time.
Questions and answers
Why does the time grow with D²/d²?
The gas to be vented scales with the pipe cross-section; the outflow scales with the blowdown cross-section.
What is the choke factor?
It allows for the extra restriction of the valve type compared with an ideal nozzle; a lubricated plug valve slows blowdown about twice.
What do the defaults represent?
An illustrative case: NPS 36 line, 12 miles, NPS 8 venturi plug. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Menon, Gas Pipeline Hydraulics (CRC Press, 2005), sec. 6.10, eqs. 6.9 and 6.10 and Example 4