Worked example
Example: Menon Example 12: 6 Mm3/day, DN 500, 60 km. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Gas flow at base conditions | 6,000,000 m³/d |
| Delivery pressure (absolute) | 5,000.0 kPa |
| Pipe inside diameter | 476.00 mm |
| Pipe length | 60.000 km |
| Pipe roughness | 0.020000 mm |
| Pipe drag factor (bends and fittings) | 0.96000 - |
| Inlet elevation | 0 m |
| Outlet elevation | 0 m |
| Gas gravity (air = 1) | 0.60000 - |
| Gas viscosity | 0.012000 cP |
| Average gas temperature | 19.850 °C |
| Compressibility factor | 0.85000 - |
| Base temperature | 14.850 °C |
| Base pressure | 101.00 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Reynolds number | 1.1347e+07 |
| Fully turbulent transmission factor | 19.779 |
| Von Kármán smooth-pipe transmission factor | 22.232 |
| Partially turbulent transmission factor | 21.342 |
| AGA transmission factor (smaller of the two) | 19.779 |
| Darcy friction factor, 4/F² | 0.010225 |
| Inlet pressure needed (absolute) | 6,129.6 kPa |
Open this example in the calculator and change any input.
Formula
\(F_r = 4\log_{10}\frac{3.7D}{e}, \quad F_t = 4\log_{10}\frac{Re}{F_t} - 0.6, \quad F_p = 4D_f\log_{10}\frac{Re}{1.4125F_t}\)
\(Q_b = 5.747\times10^{-4}F\frac{T_b}{P_b}\left(\frac{P_1^2 - e^sP_2^2}{GT_fL_eZ}\right)^{0.5}D^{2.5}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_b\) | Gas flow at base conditions | m³/s |
| \(P_2\) | Delivery pressure (absolute) | Pa |
| \(D\) | Pipe inside diameter | m |
| \(L\) | Pipe length | m |
| \(e\) | Pipe roughness | m |
| \(D_f\) | Pipe drag factor (bends and fittings) | - |
| \(H_1\) | Inlet elevation | m |
| \(H_2\) | Outlet elevation | m |
| \(G\) | Gas gravity (air = 1) | - |
| \(\mu\) | Gas viscosity | Pa·s |
| \(T_f\) | Average gas temperature | K |
| \(Z\) | Compressibility factor | - |
| \(T_b\) | Base temperature | K |
| \(P_b\) | Base pressure | Pa |
| \(Re\) | Reynolds number | - |
| \(F_r\) | Fully turbulent transmission factor | - |
| \(F_t\) | Von Kármán smooth-pipe transmission factor | - |
| \(F_p\) | Partially turbulent transmission factor | - |
| \(F\) | AGA transmission factor (smaller of the two) | - |
| \(f\) | Darcy friction factor, 4/F² | - |
| \(P_1\) | Inlet pressure needed (absolute) | Pa |
Method and standards
AGA NB-13 transmission factors in the general flow equation, in Menon's SI form (Q m³/day, P kPa, D mm, L km, T K; Re = 0.5134 (P_b/T_b)(GQ/μD) with μ in poise).
Where it is used
- Sizing a new gas transmission or plant supply line.
- Checking the pressure a compressor must deliver.
Common mistakes
- Using gauge pressures.
- Using Z at the inlet instead of the average pressure.
Assumptions and limits
- Steady isothermal flow; single slope.
References
- Menon
- Gas Pipeline Hydraulics (CRC Press, 2005)
- ch. 2
- eqs. 2.8
- 2.35 and 2.48–2.51 (AGA NB-13 method)
Questions and answers
Why two transmission factors?
AGA computes a rough-pipe value and a smooth-pipe value reduced by the drag factor, and uses the smaller one, so the flow regime chooses itself.
What drag factor should I use?
About 0.96 for bare steel with an average number of bends (bend index 60–80°), 0.975 for very few bends and 0.90–0.93 for very many.
What do the defaults represent?
Menon's Example 12: 6 million m³/day through a DN 500 line (476 mm bore), 60 km, 5 MPa delivery; the inlet needs about 6.13 MPa.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.