Worked example
Example: Illustrative 20 kg/s flare. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flared gas mass rate | 72,000 kg/h |
| Lower heating value | 46.000 MJ/kg |
| Fraction of heat radiated | 25.000 % |
| Atmospheric transmissivity | 90.000 % |
| Height of flame centre above the receptor | 60.000 m |
| Horizontal distance to the receptor | 60.000 m |
| Allowable flux at the receptor | 4.7300 kW/m² |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat release | 920.00 MW |
| Distance from flame centre | 84.853 m |
| Radiant flux at the receptor | 2.2879 kW/m² |
| Distance for the allowable flux | 59.013 m |
| Horizontal distance for the allowable flux | 0 m |
Open this example in the calculator and change any input.
Formula
\(q = \frac{\tau F\dot mLHV}{4\pi D^2}, \quad D_a = \sqrt{\frac{\tau F\dot Q}{4\pi q_a}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m\) | Flared gas mass rate | kg/s |
| \(LHV\) | Lower heating value | J/kg |
| \(F\) | Fraction of heat radiated | - |
| \(\tau\) | Atmospheric transmissivity | - |
| \(H_c\) | Height of flame centre above the receptor | m |
| \(x\) | Horizontal distance to the receptor | m |
| \(q_a\) | Allowable flux at the receptor | W/m² |
| \(\dot Q\) | Heat release | W |
| \(D\) | Distance from flame centre | m |
| \(q\) | Radiant flux at the receptor | W/m² |
| \(D_a\) | Distance for the allowable flux | m |
| \(x_a\) | Horizontal distance for the allowable flux | m |
Method and standards
Flare radiation.
Where it is used
- Flare stack height and sterile area.
- Checking equipment and personnel exposure.
Common mistakes
- Measuring distance from the stack base instead of the flame centre.
- Ignoring wind tilt of the flame.
Assumptions and limits
- Point source at the flame centre; isotropic radiation.
References
- Point-source radiation model
Questions and answers
Why is the point-source model popular?
It is simple and conservative far from the flame, the region that sets sterile areas and stack heights.
What sets the radiant fraction?
Gas composition and flame type: heavier, sootier gases radiate more; high-velocity flare tips radiate less.
What do the defaults represent?
An illustrative 20 kg/s flare of 46 MJ/kg gas, F 0.25, τ 0.9, flame centre 60 m above a receptor 60 m away, 4.73 kW/m² allowable.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crowl and Louvar, Chemical Process Safety: Fundamentals with Applications, 3rd ed. (Prentice Hall, 2011)