Cooling Water Flow for a Heat Duty

Cooling water mass and volume flow needed to remove a heat duty with a given temperature rise, using IAPWS-IF97 water enthalpy and density.

Thermal power plantSugar mill and cogenerationChemical and fertiliserPulp and paperIAPWS-IF97 (water and steam)Condenser and cooling towerPump

Inputs

Examples: Oil cooler 500 kW, 32 to 40 °CCondenser 25 MW, 32 to 41 °CProcess cooler 2 MW, 30 to 45 °C

Absolute: add the barometric pressure (about 1.013 bar) to a gauge reading, or choose a gauge unit. It matters only near boiling, where it decides whether the water stays liquid.

Results

Cooling water mass flow114,883kg/h
Cooling water volume flow (at inlet)115.37m³/h
Mean specific heat of the water4.1782kJ/(kg·K)

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Oil cooler 500 kW, 32 to 40 °C. The inputs, in the units selected above:

InputValue
Heat duty to remove500.00 kW
Cooling water inlet temperature32.000 °C
Cooling water outlet temperature40.000 °C
Water pressure (absolute)3.0000 bar

Applying the formula below gives:

ResultValue
Cooling water mass flow53,849 kg/h
Cooling water volume flow (at inlet)54.113 m³/h
Mean specific heat of the water4.1784 kJ/(kg·K)

Open this example in the calculator and change any input.

Formula

\(\dot m = \frac{\dot Q}{h(p, T_2) - h(p, T_1)} \qquad \dot V = \frac{\dot m}{\rho(p, T_1)} \qquad \bar c_p = \frac{h(T_2) - h(T_1)}{T_2 - T_1}\)

Variables

Symbol Meaning SI unit
\(\dot Q\) heat duty W
\(T_1\) water inlet temperature K
\(T_2\) water outlet temperature K
\(p\) water pressure, absolute Pa
\(\dot m\) water mass flow kg/s
\(\dot V\) water volume flow at inlet m³/s
\(\bar c_p\) mean specific heat J/(kg·K)
\(h\) water enthalpy J/kg
\(\rho\) water density kg/m³

Method and standards

Energy balance with water enthalpy and density from FireCAD's IAPWS-IF97.

Where it is used

  • Sizing cooling water for condensers, oil coolers, compressor intercoolers and process coolers.
  • Cooling water pump and pipe sizing.
  • Cooling tower load totals.

Common mistakes

  • Mixing kW and kcal/h, or m³/h and kg/s.
  • Using a design temperature rise that the cooling tower cannot deliver in summer.
  • Forgetting fouling margins on the cooler, not on the water flow.

Assumptions and limits

  • Water stays liquid; no heat loss to surroundings.

References

  • IAPWS R7-97(2012) IF97
  • first law of thermodynamics

Questions and answers

How much cooling water does a heat load need?

Heat duty divided by the water's enthalpy rise. A 500 kW oil cooler with water from 32 to 40 °C needs 14.96 kg/s, about 54 m³/h; the mean specific heat is 4.178 kJ/(kg·K).

Can I just use 4.186 kJ/(kg·K)?

Near room temperature the difference is under 0.5 %. This calculator uses the IF97 enthalpy at the actual temperatures and pressure, which stays right for hot water too.

How do I pick the temperature rise?

From the cooler design and the cooling tower: 5–10 K is common. A larger rise needs less water but a larger cooler.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.