Tube Wall Thermal Stress from Heat Flux

Temperature difference across a boiler tube or shell wall from the heat flux and the resulting thermal stress at the surfaces, E α ΔT / 2(1 − ν).

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileBoiler

Inputs

Examples: Furnace tube: 250 kW/m², 6 mm wall, k 40, E 190 GPa, alpha 13e-6, nu 0.3Shell boiler furnace: 150 kW/m², 18 mm, k 45, E 195 GPa, 12.5e-6, 0.3Superheater: 60 kW/m², 5 mm, k 28, E 170 GPa, 14e-6, 0.3

From the material standard at the mean metal temperature.

Results

Thermal stress adds to the pressure stress; the boiler code you design to sets how the two are combined and the allowable values.

Thermal stress at the surfaces (compressive on the heated side, tensile on the cooled side)66.161MPa
Temperature difference across the wall37.500K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Furnace tube: 250 kW/m², 6 mm wall, k 40, E 190 GPa, alpha 13e-6, nu 0.3. The inputs, in the units selected above:

InputValue
Heat flux through the wall250.00 kW/m²
Wall thickness6.0000 mm
Wall thermal conductivity40.000 W/(m·K)
Modulus of elasticity at metal temperature190,000 MPa
Thermal expansion coefficient13.000 µm/(m·K)
Poisson's ratio0.30000 -

Applying the formula below gives:

ResultValue
Thermal stress at the surfaces (compressive on the heated side, tensile on the cooled side)66.161 MPa
Temperature difference across the wall37.500 K

Open this example in the calculator and change any input.

Formula

\(\Delta T = \frac{q''\,t}{k} \qquad \sigma_t = \frac{E\,\alpha\,\Delta T}{2\,(1 - \nu)}\)

Variables

Symbol Meaning SI unit
\(q''\) heat flux W/m²
\(t\) wall thickness m
\(k\) conductivity W/(m·K)
\(E\) modulus of elasticity Pa
\(\alpha\) thermal expansion coefficient 1/K
\(\nu\) Poisson's ratio –
\(\sigma_t\) thermal stress at the surfaces (compressive on the heated side, tensile on the cooled side) Pa
\(\Delta T\) temperature difference across the wall K

Method and standards

Linear temperature gradient through a thin wall restrained against bending, giving equal and opposite surface stresses (Timoshenko and Goodier).

Where it is used

  • Checking heat flux limits for thick tubes and shell furnaces.
  • Start-up rate limits for drums and headers.
  • Explaining thermal fatigue cracks.

Common mistakes

  • Using room-temperature E for hot metal.
  • Ignoring thickness: the stress grows with it.
  • Comparing thermal stress alone with the allowable primary stress.

Assumptions and limits

  • Thin wall, linear gradient, elastic material; no stress concentration at holes.
  • For thick drums and headers the logarithmic temperature profile changes the surface stresses: use the thick cylinder thermal stress calculator there.

References

  • Thermal stress of a thin wall with a linear temperature gradient (Timoshenko and Goodier, Theory of Elasticity)

Questions and answers

How large is the thermal stress in a furnace tube?

250 kW/m² through a 6 mm wall with k = 40 W/(m·K) is a 37.5 K difference; with E = 190 GPa, α = 13 × 10⁻⁶/K and ν = 0.3 the stress at the surfaces is 66 MPa.

Why do thick walls crack first?

The temperature difference grows with thickness, so drums, headers and shell boiler furnaces carry far more thermal stress, especially during fast start-ups.

Is it added to the pressure stress?

Yes, as a secondary stress; the code you design to sets how they combine and what fatigue life follows.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.