FireCADCalc

Flow Split between Parallel Tubes (Superheater Passes)

Flow in each of up to three parallel tubes between common headers from their bores, equivalent lengths and friction factors (equal pressure drop), Ganapathy Q3.25.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperBoiler

Inputs

Examples: Ganapathy: three superheater passes, 15,000 lb/hTwo tubes

Results

Check the metal temperature of the tube with the least flow.

Flow in tube 11,933.2kg/h
Flow in tube 21,695.5kg/h
Flow in tube 30kg/h
Lowest flow relative to the mean93.450%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Ganapathy: three superheater passes, 15,000 lb/h. The inputs, in the units selected above:

InputValue
Total flow6,803.9 kg/h
Tube 1 inner diameter50.800 mm
Tube 1 equivalent length121.92 m
Tube 1 friction factor0.019500 -
Tube 2 inner diameter44.450 mm
Tube 2 equivalent length106.68 m
Tube 2 friction factor0.020000 -
Tube 3 inner diameter (0 = none)50.800 mm
Tube 3 equivalent length112.78 m
Tube 3 friction factor0.019500 -

Applying the formula below gives:

ResultValue
Flow in tube 12,433.7 kg/h
Flow in tube 21,839.8 kg/h
Flow in tube 32,530.4 kg/h
Lowest flow relative to the mean81.123 %

Open this example in the calculator and change any input.

Formula

\(\Delta p \propto \frac{f L W^2}{d^5} \Rightarrow W_i = W\frac{\sqrt{d_i^5/(f_iL_i)}}{\sum_j\sqrt{d_j^5/(f_jL_j)}}, \quad \frac{W_{min}}{\bar W} = \frac{n\,\min_i W_i}{W}\)

Variables

Symbol Meaning SI unit
\(W\) Total flow kg/s
\(d_1\) Tube 1 inner diameter m
\(L_1\) Tube 1 equivalent length m
\(f_1\) Tube 1 friction factor -
\(d_2\) Tube 2 inner diameter m
\(L_2\) Tube 2 equivalent length m
\(f_2\) Tube 2 friction factor -
\(d_3\) Tube 3 inner diameter (0 = none) m
\(L_3\) Tube 3 equivalent length m
\(f_3\) Tube 3 friction factor -
\(W_1\) Flow in tube 1 kg/s
\(W_2\) Flow in tube 2 kg/s
\(W_3\) Flow in tube 3 kg/s
\(W_{min}/\bar W\) Lowest flow relative to the mean -
\(n\) number of tubes (2, or 3 when d_3 > 0) -

Method and standards

Equal pressure drop in parallel passes.

Where it is used

  • Superheater and reheater design.
  • Economiser and furnace circuit checks.

Common mistakes

  • Ignoring header pressure gradients.
  • Using actual instead of equivalent length.

Assumptions and limits

  • Same fluid properties in all tubes; header pressure drop neglected. In a superheater the low-flow tube runs hotter, so its steam is lighter and its pressure drop per kg higher, which cuts its flow further: the split found here is optimistic for the worst tube.

References

  • Ganapathy
  • Steam Plant Calculations Manual
  • 2nd ed. (Marcel Dekker, 1993)
  • Q3.25 (flow in parallel passes of a superheater)
  • Darcy pressure drop Δp ∝ f L W²/d⁵ at equal properties

Questions and answers

Why do parallel tubes share flow unequally?

Each tube must have the same header-to-header pressure drop, so longer or smaller tubes carry less.

Why does it matter?

The tube with least steam runs hottest; a superheater can fail there first.

What did Ganapathy find?

Three tubes sharing 15,000 lb/h took about 5,350, 4,050 and 5,590 lb/h.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.