Concentrated Spent Wash: As-Fired Gross and Net Value

As-fired gross and net calorific value of concentrated spent wash from its dry-solids GCV, solids content and hydrogen, with IF97 latent heat at 25 °C.

Sugar mill and cogenerationDistillery and ethanolIAPWS-IF97 (water and steam)

Inputs

Examples: 55 % solids60 % solids

Results

As-fired GCV7,425.0kJ/kg
As-fired NCV5,786.2kJ/kg
Latent heat of water at 25 °C2,441.7kJ/kg

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 55 % solids. The inputs, in the units selected above:

InputValue
GCV of dry solids (lab)13,500 kJ/kg
Solids in concentrate55.000 %
Hydrogen % dry solids4.5000 %

Applying the formula below gives:

ResultValue
As-fired GCV7,425.0 kJ/kg
As-fired NCV5,786.2 kJ/kg
Latent heat of water at 25 °C2,441.7 kJ/kg

Open this example in the calculator and change any input.

Formula

\(GCV = x\,GCV_d, \quad NCV = GCV - h_{fg,25}\left[(1-x) + x\,H\,\frac{M_{H_2O}}{M_{H_2}}\right]\)

Variables

Symbol Meaning SI unit
\(GCV_d\) GCV of dry solids (lab) J/kg
\(x\) Solids in concentrate -
\(H\) Hydrogen % dry solids -
\(GCV\) As-fired GCV J/kg
\(NCV\) As-fired NCV J/kg
\(h_{fg,25}\) Latent heat of water at 25 °C J/kg

Method and standards

Gross-to-net conversion.

Where it is used

  • Incineration boiler fuel planning.
  • Evaporator target solids.

Common mistakes

  • Wet-basis GCV entered as dry.

Assumptions and limits

  • 25 °C reference.
  • Only the latent-heat term of the gross-to-net conversion is applied; the small constant-volume to constant-pressure terms of ISO 1928 (oxygen, nitrogen) are left out.

References

  • Net value = gross − latent heat × (moisture + water formed from hydrogen) at 25 °C (the latent-heat term of ISO 1928; its constant-volume to constant-pressure corrections for oxygen and nitrogen are omitted); latent heat from IAPWS-IF97; GCV of dry solids by bomb calorimeter

Questions and answers

Why measure the dry solids' GCV?

Spent wash solids vary with molasses and process; no general formula is reliable.

Why does solids content matter so much?

Every kg of water takes about 2.44 MJ to evaporate.

Hydrogen?

Hydrogen burns to water, which also leaves as vapour in the net value.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.