Worked example
Example: Deaerator at 105 °C (saturated), 8 m above the pump, 0.6 m losses, NPSHr 5 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pressure on the liquid surface (absolute) | 1.2090 bar |
| Water temperature | 105.00 °C |
| Liquid level above the pump centreline (negative for a lift) | 8.0000 m |
| Friction loss in the suction line | 0.60000 m |
| NPSH required by the pump (0 = skip) | 5.0000 m |
Applying the formula below gives:
| Result | Value |
|---|---|
| NPSH available | 7.4000 m |
| Margin over NPSH required | 2.4000 m |
| Head from pressure above vapour pressure | 0 m |
| Vapour pressure of water | 1.2090 bar |
| Water density | 954.71 kg/m³ |
Open this example in the calculator and change any input.
Formula
\(NPSH_a = \frac{p_s - p_v}{\rho\,g} + z - h_f\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p_s\) | absolute pressure on the liquid surface | Pa |
| \(T\) | water temperature | K |
| \(z\) | liquid level above the pump centreline (negative for a lift) | m |
| \(h_f\) | friction loss in the suction line | m |
| \(NPSH_r\) | NPSH required by the pump | m |
| \(NPSH_a\) | NPSH available | m |
| \(NPSH_a - NPSH_r\) | margin (the ratio NPSHa/NPSHr is given in a note) | m |
| \(h_p\) | head from pressure above the vapour pressure | m |
| \(p_v\) | vapour pressure of water at \(T\) | Pa |
| \(\rho\) | density of saturated water at \(T\) | kg/m³ |
| \(g\) | standard gravity, 9.806 65 | m/s² |
Method and standards
The definition of NPSH available of ANSI/HI 9.6.1, referred to the pump centreline. Vapour pressure and liquid density come from FireCAD's IAPWS-IF97 implementation on the saturation line at the water temperature.
Where it is used
- Checking feed pump suction from the deaerator.
- Condensate extraction and hot water transfer pumps.
- Setting the deaerator or tank elevation.
Common mistakes
- Using the tank pressure when the liquid is at saturation: NPSH available is then only static head less losses.
- Ignoring the transient when a deaerator's pressure falls suddenly.
- Comparing NPSH available with NPSH required without a margin.
Assumptions and limits
- Water only (0.01 °C to 350 °C).
- Lowest liquid level and highest temperature are the design case; use them.
- Velocity head at the suction flange is included in the friction loss you enter, as is common practice.
- Dissolved gas and transient pressure decay in a deaerator on load rejection are not covered; they need extra margin.
References
- ANSI/HI 9.6.1 (NPSH margin)
- IAPWS R7-97(2012) IF97 (vapour pressure, density)
Questions and answers
How is NPSH available calculated?
NPSHa = (surface pressure − vapour pressure)/(ρ·g) + static height − suction friction. For an open tank of water at 30 °C, 2 m above the pump with 0.5 m of losses, NPSHa = 9.94 + 2 − 0.5 = 11.4 m.
Why must a deaerator be mounted high?
The water in a deaerator is at its boiling point, so the pressure term is zero and the only NPSH comes from the height. With the deaerator 8 m above the pump and 0.6 m of suction losses, NPSHa is 7.4 m.
How much margin over NPSH required is needed?
ANSI/HI 9.6.1 gives margin ratios by pump type and service. The calculator shows the difference; the margin to accept is the standard's or the pump maker's.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.