Worked example
Example: 20 people, process, 1000 m³/h humid air. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Number of people | 20.000 - |
| Moisture per person | 0.070000 kg/h |
| Evaporation from processes | 1.0000 kg/h |
| Outdoor air entering (infiltration or fresh air) | 1,000.0 m³/h |
| Outdoor dry bulb | 35.000 °C |
| Outdoor relative humidity | 60.000 % |
| Indoor dry bulb | 24.000 °C |
| Indoor relative humidity | 50.000 % |
| Barometric pressure (absolute) | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Moisture from outdoor air | 13.448 kg/h |
| Total moisture load | 15.848 kg/h |
| Latent heat at the indoor temperature (IF97) | 2,444.1 kJ/kg |
| Latent load | 10.759 kW |
Open this example in the calculator and change any input.
Formula
\(\dot m_t = n g_p + \dot m_p + \dot m_{da}(W_o - W_i), \quad \dot Q_l = \dot m_t h_{fg}(T_i)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(n\) | Number of people | - |
| \(g_p\) | Moisture per person | kg/s |
| \(\dot m_p\) | Evaporation from processes | kg/s |
| \(\dot V_o\) | Outdoor air entering (infiltration or fresh air) | m³/s |
| \(T_o\) | Outdoor dry bulb | K |
| \(\varphi_o\) | Outdoor relative humidity | - |
| \(T_i\) | Indoor dry bulb | K |
| \(\varphi_i\) | Indoor relative humidity | - |
| \(p\) | Barometric pressure (absolute) | Pa |
| \(\dot m_o\) | Moisture from outdoor air | kg/s |
| \(\dot m_t\) | Total moisture load | kg/s |
| \(h_{fg}\) | Latent heat at the indoor temperature (IF97) | J/kg |
| \(\dot Q_l\) | Latent load | W |
Method and standards
Moisture balance.
Where it is used
- Latent load for control rooms, labs and process halls.
- Dehumidifier sizing.
Common mistakes
- Counting outdoor air twice (infiltration and fresh air).
- Moisture per person at the wrong activity.
Assumptions and limits
- Steady state.
- The latent heat is h_fg at the indoor temperature from IF97 (about 2 444 kJ/kg at 24 °C). The dehumidifier calculator uses the psychrometric convention of 2 501 kJ/kg, so the same moisture gives a latent load about 2 % higher there.
References
- Moisture balance; latent heat of vaporisation from IAPWS-IF97 at the room temperature
Questions and answers
What does the default room add?
About 1.4 kg/h from people, 1 kg/h from the process and roughly 13 kg/h from 1000 m³/h of humid outdoor air.
Why use h_fg at room temperature?
The water vapour condenses on the coil from the room's state; the difference from 2501 kJ/kg is small.
Dry climates?
Outdoor air may remove moisture; the result shows it as negative.