Room Moisture Load and Latent Heat (People, Process, Outdoor Air)

Moisture added to a room by people, open processes and outdoor air, and the latent cooling load to remove it, from rates you enter and the air states.

IAPWS-IF97 (water and steam)

Inputs

Examples: 20 people, process, 1000 m³/h humid airSealed room: people onlyDry outdoor air removes moisture

From a handbook for the activity; your figure.

Results

Moisture from outdoor air13.448kg/h
Total moisture load15.848kg/h
Latent heat at the indoor temperature (IF97)2,444.1kJ/kg
Latent load10.759kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 20 people, process, 1000 m³/h humid air. The inputs, in the units selected above:

InputValue
Number of people20.000 -
Moisture per person0.070000 kg/h
Evaporation from processes1.0000 kg/h
Outdoor air entering (infiltration or fresh air)1,000.0 m³/h
Outdoor dry bulb35.000 °C
Outdoor relative humidity60.000 %
Indoor dry bulb24.000 °C
Indoor relative humidity50.000 %
Barometric pressure (absolute)101.33 kPa

Applying the formula below gives:

ResultValue
Moisture from outdoor air13.448 kg/h
Total moisture load15.848 kg/h
Latent heat at the indoor temperature (IF97)2,444.1 kJ/kg
Latent load10.759 kW

Open this example in the calculator and change any input.

Formula

\(\dot m_t = n g_p + \dot m_p + \dot m_{da}(W_o - W_i), \quad \dot Q_l = \dot m_t h_{fg}(T_i)\)

Variables

Symbol Meaning SI unit
\(n\) Number of people -
\(g_p\) Moisture per person kg/s
\(\dot m_p\) Evaporation from processes kg/s
\(\dot V_o\) Outdoor air entering (infiltration or fresh air) m³/s
\(T_o\) Outdoor dry bulb K
\(\varphi_o\) Outdoor relative humidity -
\(T_i\) Indoor dry bulb K
\(\varphi_i\) Indoor relative humidity -
\(p\) Barometric pressure (absolute) Pa
\(\dot m_o\) Moisture from outdoor air kg/s
\(\dot m_t\) Total moisture load kg/s
\(h_{fg}\) Latent heat at the indoor temperature (IF97) J/kg
\(\dot Q_l\) Latent load W

Method and standards

Moisture balance.

Where it is used

  • Latent load for control rooms, labs and process halls.
  • Dehumidifier sizing.

Common mistakes

  • Counting outdoor air twice (infiltration and fresh air).
  • Moisture per person at the wrong activity.

Assumptions and limits

  • Steady state.
  • The latent heat is h_fg at the indoor temperature from IF97 (about 2 444 kJ/kg at 24 °C). The dehumidifier calculator uses the psychrometric convention of 2 501 kJ/kg, so the same moisture gives a latent load about 2 % higher there.

References

  • Moisture balance; latent heat of vaporisation from IAPWS-IF97 at the room temperature

Questions and answers

What does the default room add?

About 1.4 kg/h from people, 1 kg/h from the process and roughly 13 kg/h from 1000 m³/h of humid outdoor air.

Why use h_fg at room temperature?

The water vapour condenses on the coil from the room's state; the difference from 2501 kJ/kg is small.

Dry climates?

Outdoor air may remove moisture; the result shows it as negative.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.