Worked example
Example: Sea level, 20 °C, 50 % RH. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air temperature (dry bulb) | 20.000 °C |
| Relative humidity | 50.000 % |
| Pressure from | Altitude (ISO 2533 standard atmosphere) |
| Site altitude above sea level | 0 m |
| Barometric pressure (absolute) | 1.0132 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Density of the humid air | 1.1989 kg/m³ |
| Density of dry air at the same pressure and temperature | 1.2042 kg/m³ |
| Humidity ratio | 7.2629 g/kg |
| Partial pressure of water vapour | 1.1696 kPa |
| Saturation pressure of water | 2.3392 kPa |
| Barometric pressure used | 101.33 kPa |
Open this example in the calculator and change any input.
Formula
\(p_v = \varphi\,p_{sat}(T) \qquad \rho = \frac{(p - p_v)\,M_{da} + p_v\,M_w}{R\,T} \qquad \rho_{da} = \frac{p\,M_{da}}{R\,T} \qquad W = \frac{M_w}{M_{da}}\cdot\frac{p_v}{p - p_v}\)
Site pressure from the ISO 2533 standard atmosphere:
\(p = p_0\left(1 - \frac{L\,z}{T_0}\right)^{\frac{g\,M_{ISA}}{R^*\,L}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T\) | air temperature (dry bulb) | K |
| \(\varphi\) | relative humidity | – |
| \(\text{site}\) | pressure from altitude or entered | – |
| \(z\) | site altitude above sea level | m |
| \(p_s\) | barometric pressure entered | Pa |
| \(\rho\) | density of the humid air | kg/m³ |
| \(\rho_{da}\) | density of dry air at the same pressure and temperature | kg/m³ |
| \(W\) | humidity ratio, water vapour per kg of dry air | kg/kg |
| \(p_v\) | partial pressure of water vapour | Pa |
| \(p_{sat}\) | saturation pressure of water at \(T\) | Pa |
| \(p\) | barometric pressure used | Pa |
| \(M_{da}\), \(M_w\) | molar mass of dry air (about 28.966, computed from the PTC 4 composition) and water (18.015) | kg/kmol |
| \(R\) | universal gas constant, 8.314 462 618 | J/(mol·K) |
| \(p_0\), \(T_0\), \(L\), \(M_{ISA}\), \(R^*\), \(g\) | ISO 2533 constants: 101 325 Pa, 288.15 K, 0.0065 K/m, 28.964 42 kg/kmol, 8.314 32 J/(mol·K), 9.806 65 m/s² | – |
Method and standards
Humid air as an ideal mixture of dry air and water vapour (Dalton). Saturation pressure of water from FireCAD's IAPWS-IF97 region 4 equation; dry-air molar mass from the ASME PTC 4-2013 composition with IUPAC atomic weights; site pressure from ISO 2533:1975.
Where it is used
- Fan sizing at site altitude and temperature.
- Combustion air and draught calculations.
- Correcting flow meter readings.
Common mistakes
- Using sea-level density at a high site.
- Ignoring humidity in hot, humid climates.
- Using gauge pressure as absolute.
Assumptions and limits
- 0 °C to 100 °C (the IF97 saturation line starts at 0 °C; over ice is not covered).
- Ideal gas, no enhancement factor: the density error is below 0.1 % at atmospheric pressure.
- Standard-atmosphere pressure is a long-term mean; weather moves the actual pressure by ±2 %.
References
- ISO 2533:1975 (standard atmosphere)
- IAPWS R7-97(2012) IF97 (saturation pressure)
- ASME PTC 4-2013 (dry air composition)
Questions and answers
What is the density of air?
1.199 kg/m³ at 20 °C, 50 % relative humidity and sea-level pressure; 1.292 kg/m³ for dry air at 0 °C. It falls with temperature, altitude and humidity.
Why is humid air lighter than dry air?
Water vapour (18.015 kg/kmol) is lighter than the air it displaces (28.97 kg/kmol). At 35 °C and 80 % humidity the air is 1.7 % lighter than dry air.
How does altitude affect a fan?
At 900 m the standard pressure is 909.7 hPa, about 10 % below sea level. A fan at the same speed moves the same volume but 10 % less mass, with 10 % less pressure and power.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.