FireCADCalc

Fire Plume Smoke Production and Extract Rate (Zukoski, Heskestad)

Flame height and plume mass flow at a clear height above a fire, the smoke temperature rise and the volume a smoke extract system must remove.

Process steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Illustrative 2.5 MW fire, 6 m clear heightAtrium 5 MW, 12 mOffice 1 MW, 3 m

Accepted: 0.01 to 100 MW
Accepted: 40 to 100 %
Accepted: 0.1 to 20 m
Accepted: 1 to 100 m
Accepted: -10 to 50 °C

Results

Heskestad flame height L_f = 0.235Q^(2/5) − 1.02D (Q in kW, m); Zukoski plume ṁ = 0.071Q_c^(1/3)z^(5/3) (kg/s, kW, m) above the flame. Smoke temperature rise ΔT = Q_c/(ṁc_p); extract volume = ṁ/ρ_s with ρ_s ≈ 353/T. Smoke production rises steeply with clear height, so keeping the layer high costs a lot of extract. Design fires and codes come from the user's fire engineering basis.

Mean flame height1.6845m
Plume mass flow at the clear height3.9339kg/s
Smoke temperature rise177.05K
Smoke volume flow to extract5.2401m³/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 2.5 MW fire, 6 m clear height. The inputs, in the units selected above:

InputValue
Total heat release rate2.5000 MW
Convective fraction70.000 %
Fire diameter3.0000 m
Clear height above the fire base6.0000 m
Ambient temperature20.000 °C

Applying the formula below gives:

ResultValue
Mean flame height2.3133 m
Plume mass flow at the clear height16.951 kg/s
Smoke temperature rise102.73 K
Smoke volume flow to extract19.010 m³/s

Open this example in the calculator and change any input.

Formula

\(L_f = 0.235\dot Q^{2/5} - 1.02D, \quad \dot m_p = 0.071\dot Q_c^{1/3}z^{5/3}, \quad \Delta T_s = \frac{\dot Q_c}{\dot m_pc_p}\)

Variables

Symbol Meaning SI unit
\(\dot Q\) Total heat release rate W
\(\chi_c\) Convective fraction -
\(D\) Fire diameter m
\(z\) Clear height above the fire base m
\(T_0\) Ambient temperature K
\(L_f\) Mean flame height m
\(\dot m_p\) Plume mass flow at the clear height kg/s
\(\Delta T_s\) Smoke temperature rise K
\(\dot V_s\) Smoke volume flow to extract m³/s

Method and standards

Smoke production.

Where it is used

  • Atrium, mall and warehouse smoke control.
  • Smoke reservoir and extract fan sizing.

Common mistakes

  • Using total instead of convective heat release.
  • Applying the far-field plume within the flames.

Assumptions and limits

  • Axisymmetric plume in quiescent air; above the mean flame height.

References

  • Axisymmetric fire plume correlations
  • Heskestad
  • Fire plumes
  • flame height and air entrainment
  • in SFPE Handbook of Fire Protection Engineering (method)

Questions and answers

Why does smoke volume rise with clear height?

The plume entrains air all the way up, so the higher the smoke layer is kept, the more air-smoke mixture must be removed.

Where does the fire size come from?

From the design fire in the fire strategy, for example 1–5 MW for offices and shops, more for warehouses.

What do the defaults represent?

An illustrative 2.5 MW fire, 70 % convective, 3 m diameter, with a 6 m clear height in 20 °C air.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Zukoski, Development of a stratified ceiling layer in the early stages of a closed-room fire, Fire and Materials 2, 54 (1978)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.