Worked example
Example: Illustrative 2.5 MW fire, 6 m clear height. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Total heat release rate | 2.5000 MW |
| Convective fraction | 70.000 % |
| Fire diameter | 3.0000 m |
| Clear height above the fire base | 6.0000 m |
| Ambient temperature | 20.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Mean flame height | 2.3133 m |
| Plume mass flow at the clear height | 16.951 kg/s |
| Smoke temperature rise | 102.73 K |
| Smoke volume flow to extract | 19.010 m³/s |
Open this example in the calculator and change any input.
Formula
\(L_f = 0.235\dot Q^{2/5} - 1.02D, \quad \dot m_p = 0.071\dot Q_c^{1/3}z^{5/3}, \quad \Delta T_s = \frac{\dot Q_c}{\dot m_pc_p}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q\) | Total heat release rate | W |
| \(\chi_c\) | Convective fraction | - |
| \(D\) | Fire diameter | m |
| \(z\) | Clear height above the fire base | m |
| \(T_0\) | Ambient temperature | K |
| \(L_f\) | Mean flame height | m |
| \(\dot m_p\) | Plume mass flow at the clear height | kg/s |
| \(\Delta T_s\) | Smoke temperature rise | K |
| \(\dot V_s\) | Smoke volume flow to extract | m³/s |
Method and standards
Smoke production.
Where it is used
- Atrium, mall and warehouse smoke control.
- Smoke reservoir and extract fan sizing.
Common mistakes
- Using total instead of convective heat release.
- Applying the far-field plume within the flames.
Assumptions and limits
- Axisymmetric plume in quiescent air; above the mean flame height.
References
- Axisymmetric fire plume correlations
- Heskestad
- Fire plumes
- flame height and air entrainment
- in SFPE Handbook of Fire Protection Engineering (method)
Questions and answers
Why does smoke volume rise with clear height?
The plume entrains air all the way up, so the higher the smoke layer is kept, the more air-smoke mixture must be removed.
Where does the fire size come from?
From the design fire in the fire strategy, for example 1–5 MW for offices and shops, more for warehouses.
What do the defaults represent?
An illustrative 2.5 MW fire, 70 % convective, 3 m diameter, with a 6 m clear height in 20 °C air.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Zukoski, Development of a stratified ceiling layer in the early stages of a closed-room fire, Fire and Materials 2, 54 (1978)