Worked example
Example: Round duct 800 mm, 8 m³/s air, 60 m, K 1.5. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Duct shape | Round |
| Inside diameter (round) | 800.00 mm |
| Inside width (rectangular) | 0 mm |
| Inside height (rectangular) | 0 mm |
| Duct length | 60.000 m |
| Volume flow (actual) | 28,800 m³/h |
| Gas density | 1.1500 kg/m³ |
| Dynamic viscosity | 1.8500e-05 Pa·s |
| Wall roughness | 0.15000 mm |
| Sum of fitting loss coefficients | 1.5000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total pressure drop | 38.725 mmWC |
| Friction in straight duct | 16.447 mmWC |
| Loss in fittings | 22.278 mmWC |
| Velocity | 15.915 m/s |
| Velocity pressure | 14.852 mmWC |
| Reynolds number | 791,473 |
| Darcy friction factor | 0.014765 |
| Hydraulic diameter | 800.00 mm |
Open this example in the calculator and change any input.
Formula
\(D_h = D\ \text{(round)},\ \ \frac{2ab}{a+b}\ \text{(rectangular)} \qquad v = \frac{\dot V}{A} \qquad Re = \frac{\rho\,v\,D_h}{\mu} \qquad p_d = \frac{\rho v^2}{2}\)
\(\frac{1}{\sqrt f} = -2\log_{10}\!\left(\frac{\varepsilon/D_h}{3.7} + \frac{2.51}{Re\sqrt f}\right) \qquad \Delta p_f = f\,\frac{L}{D_h}\,p_d \qquad \Delta p_K = \Sigma K\,p_d \qquad \Delta p = \Delta p_f + \Delta p_K\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{shape}\) | round or rectangular | – |
| \(D\) | inside diameter, round duct | m |
| \(a\) | inside width, rectangular duct | m |
| \(b\) | inside height, rectangular duct | m |
| \(L\) | duct length | m |
| \(\dot V\) | actual volume flow | m³/s |
| \(\rho\) | gas density | kg/m³ |
| \(\mu\) | dynamic viscosity | Pa·s |
| \(\varepsilon\) | wall roughness | m |
| \(\Sigma K\) | sum of fitting loss coefficients | – |
| \(\Delta p\) | total pressure drop | Pa |
| \(\Delta p_f\) | friction in straight duct | Pa |
| \(\Delta p_K\) | loss in fittings | Pa |
| \(v\) | velocity | m/s |
| \(p_d\) | velocity pressure | Pa |
| \(Re\) | Reynolds number | – |
| \(f\) | Darcy friction factor | – |
| \(D_h\) | hydraulic diameter | m |
| \(A\) | flow area | m² |
Method and standards
Darcy–Weisbach with the Colebrook–White friction factor (laminar 64/Re), on the hydraulic diameter, as in the Duct Design chapter of the ASHRAE Handbook—Fundamentals. Fittings by loss coefficients on the duct velocity pressure.
Where it is used
- Sizing air and flue gas ducts.
- Estimating fan pressure.
- Checking duct modifications.
Common mistakes
- Using standard air density for hot gas.
- Forgetting bends, dampers and transitions.
- Using hydraulic diameter wrongly for rectangular ducts.
Assumptions and limits
- Constant density along the duct (pressure changes small against absolute pressure).
- Fully developed turbulent flow; loss coefficients of fittings close together interact and are approximate.
- Laminar 64/Re below Re 2 300, Colebrook above; the transitional range 2 300–4 000 (Colebrook, conservative) is flagged.
- For flat ducts (aspect ratio above about 4) the hydraulic-diameter method slightly underestimates friction.
References
- Darcy–Weisbach equation
- Colebrook (1939)
- ASHRAE Handbook—Fundamentals (2017)
- ch. 21 (Duct Design)
Questions and answers
How is duct pressure drop calculated?
Δp = (f·L/D_h + ΣK)·ρv²/2, with f from Colebrook at the duct's Reynolds number and relative roughness. 20 m³/s of air in a 1 600 × 1 000 mm duct over 40 m with ΣK = 2 loses 220 Pa, most of it in the fittings.
Hydraulic or equivalent diameter?
This calculator uses the hydraulic diameter with the true velocity in the duct, which gives the same friction as Huebscher's equivalent diameter with the volume flow.
What roughness should I use?
About 0.15 mm for galvanised sheet ducts (ASHRAE); plain steel plate ducts with scale or ash deposits are rougher, often 0.5 mm or more.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.