FireCADCalc

Chilled Water Flow Rate from Cooling Load

Chilled or condenser water flow for a cooling load and temperature difference, in m³/h, L/s and US gpm, with water properties from IAPWS-IF97.

Refinery and petrochemicalChemical and fertiliserFood, dairy and textileIAPWS-IF97 (water and steam)PumpAir conditioning and chillersRefrigeration and air-conditioning mechanic examinations

Inputs

Examples: 500 TR, 7 to 12 °C, 4 bar(a)1000 kW, 6 to 12 °C, 3 bar(a)Condenser water 2000 kW, 32 to 37 °C, 3 bar(a)

Results

Volume flow is at the supply temperature.

Water mass flow301,788kg/h
Water volume flow301.77m³/h
Water volume flow, US gpm1,328.7US gal/min
Mean specific heat (enthalpy difference over ΔT)4.1952kJ/(kg·K)

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 500 TR, 7 to 12 °C, 4 bar(a). The inputs, in the units selected above:

InputValue
Cooling load500.00 TR
Supply water temperature7.0000 °C
Return water temperature12.000 °C
Water pressure (absolute)4.0000 bar

Applying the formula below gives:

ResultValue
Water mass flow301,788 kg/h
Water volume flow301.77 m³/h
Water volume flow, US gpm1,328.7 US gal/min
Mean specific heat (enthalpy difference over ΔT)4.1952 kJ/(kg·K)

Open this example in the calculator and change any input.

Formula

\(\dot m = \frac{\dot Q}{h(T_r) - h(T_s)} \qquad \dot V = \frac{\dot m}{\rho(T_s)} \qquad \bar c_p = \frac{h(T_r) - h(T_s)}{T_r - T_s}\)

Variables

Symbol Meaning SI unit
\(\dot Q\) cooling load W
\(T_s\) supply temperature K
\(T_r\) return temperature K
\(p\) water pressure Pa
\(\dot m\) mass flow kg/s
\(\dot V\) volume flow m³/s
\(\dot V_{gpm}\) volume flow in US gpm m³/s
\(\bar c_p\) mean specific heat J/(kg·K)
\(h, \rho\) IF97 enthalpy and density J/kg, kg/m³

Method and standards

Energy balance with IAPWS-IF97 liquid enthalpies; the volume flow is at the supply temperature.

Where it is used

  • Chiller and AHU piping design.
  • Condenser water pumps.
  • Process cooling water circuits.

Common mistakes

  • Using a 10 °F rule on a 5 K system.
  • Mixing kW and TR.
  • Forgetting glycol (lower specific heat) in brine circuits.

Assumptions and limits

  • Plain water; for glycol mixtures use the maker's specific heat.

References

  • IAPWS-IF97

Questions and answers

What flow does a 500 TR chiller need at 7/12 °C?

84 kg/s, or about 302 m³/h (1329 US gpm).

Is 2.4 gpm per ton right?

That rule comes from a 10 °F (5.6 K) range; at 5 K it is about 2.7 gpm per ton.

Why use IF97 instead of 4.187?

The specific heat of water varies a little with temperature; IF97 enthalpies give the exact energy balance.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.