Worked example
Example: 500 TR, 7 to 12 °C, 4 bar(a). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Cooling load | 500.00 TR |
| Supply water temperature | 7.0000 °C |
| Return water temperature | 12.000 °C |
| Water pressure (absolute) | 4.0000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Water mass flow | 301,788 kg/h |
| Water volume flow | 301.77 m³/h |
| Water volume flow, US gpm | 1,328.7 US gal/min |
| Mean specific heat (enthalpy difference over ΔT) | 4.1952 kJ/(kg·K) |
Open this example in the calculator and change any input.
Formula
\(\dot m = \frac{\dot Q}{h(T_r) - h(T_s)} \qquad \dot V = \frac{\dot m}{\rho(T_s)} \qquad \bar c_p = \frac{h(T_r) - h(T_s)}{T_r - T_s}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q\) | cooling load | W |
| \(T_s\) | supply temperature | K |
| \(T_r\) | return temperature | K |
| \(p\) | water pressure | Pa |
| \(\dot m\) | mass flow | kg/s |
| \(\dot V\) | volume flow | m³/s |
| \(\dot V_{gpm}\) | volume flow in US gpm | m³/s |
| \(\bar c_p\) | mean specific heat | J/(kg·K) |
| \(h, \rho\) | IF97 enthalpy and density | J/kg, kg/m³ |
Method and standards
Energy balance with IAPWS-IF97 liquid enthalpies; the volume flow is at the supply temperature.
Where it is used
- Chiller and AHU piping design.
- Condenser water pumps.
- Process cooling water circuits.
Common mistakes
- Using a 10 °F rule on a 5 K system.
- Mixing kW and TR.
- Forgetting glycol (lower specific heat) in brine circuits.
Assumptions and limits
- Plain water; for glycol mixtures use the maker's specific heat.
References
- IAPWS-IF97
Questions and answers
What flow does a 500 TR chiller need at 7/12 °C?
84 kg/s, or about 302 m³/h (1329 US gpm).
Is 2.4 gpm per ton right?
That rule comes from a 10 °F (5.6 K) range; at 5 K it is about 2.7 gpm per ton.
Why use IF97 instead of 4.187?
The specific heat of water varies a little with temperature; IF97 enthalpies give the exact energy balance.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.