Worked example
Example: Illustrative 400 kW load, 250 kW wind. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Load | 400.00 kW |
| Wind power available | 250.00 kW |
| Diesel rated power | 500.00 kW |
| Diesel minimum load (fraction of rating) | 30.000 % |
| Fuel curve no-load coefficient (L per kWh of rating) | 0.084150 - |
| Fuel curve slope (L per kWh of output) | 0.24600 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Diesel output with wind | 150.00 kW |
| Wind power used | 250.00 kW |
| Wind power dumped | 0 kW |
| Fuel without wind (L/h) | 140.47 |
| Fuel with wind (L/h) | 78.975 |
| Fuel saving | 43.780 % |
Open this example in the calculator and change any input.
Formula
\(P_d = \max(f_{min}P_r,\;P_L - P_w), \quad F = aP_r + bP_d\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_L\) | Load | W |
| \(P_w\) | Wind power available | W |
| \(P_r\) | Diesel rated power | W |
| \(f_{min}\) | Diesel minimum load (fraction of rating) | - |
| \(a\) | Fuel curve no-load coefficient (L per kWh of rating) | - |
| \(b\) | Fuel curve slope (L per kWh of output) | - |
| \(P_d\) | Diesel output with wind | W |
| \(P_{w,used}\) | Wind power used | W |
| \(P_{dump}\) | Wind power dumped | W |
| \(F_0\) | Fuel without wind (L/h) | - |
| \(F\) | Fuel with wind (L/h) | - |
| \(1 - F/F_0\) | Fuel saving | - |
Method and standards
Hybrid dispatch.
Where it is used
- Island and mine power systems.
- Screening wind retrofits to diesel grids.
Common mistakes
- Assuming fuel falls in proportion to output.
- Ignoring spinning reserve requirements.
Assumptions and limits
- One diesel running; steady snapshot.
References
- Linear diesel fuel curve with minimum load
Questions and answers
Why is the saving less than the wind share?
A running diesel burns fuel even at no load, and it cannot go below its minimum load, so some wind is dumped.
How can more wind be used?
Run fewer or smaller diesels, add batteries or a flywheel, and use surplus wind for heating or water pumping.
What do the defaults represent?
An illustrative 400 kW load, 250 kW of wind and a 500 kW diesel with a 30 % minimum load and a generic fuel curve.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Manwell, McGowan and Rogers, Wind Energy Explained, 2nd ed. (Wiley, 2009), ch. 9