Worked example
Example: Illustrative 150 F, 48 to 24 V, 6 mOhm, 5 kW. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Capacitance | 1.5000e+08 µF |
| Starting voltage | 48.000 V |
| Minimum voltage | 24.000 V |
| Equivalent series resistance | 0.006000 Ω |
| Constant load power | 5.0000 kW |
Applying the formula below gives:
| Result | Value |
|---|---|
| Energy stored at V_max | 172.80 kJ |
| Usable energy between V_max and V_min | 129.60 kJ |
| Usable fraction | 75.000 % |
| Discharge time ignoring resistance | 25.920 s |
| Discharge time with resistance | 25.277 s |
| Starting current | 105.56 A |
| Final current | 220.49 A |
| Energy lost in the resistance | 3.2134 kJ |
Open this example in the calculator and change any input.
Formula
\(E_u = \frac{1}{2}C\left(V_{max}^2 - V_{min}^2\right), \quad I = \frac{V - \sqrt{V^2 - 4PR}}{2R}, \quad t = \int_{V_{min}}^{V_{max}}\frac{C\,dV}{I}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C\) | Capacitance | F |
| \(V_{max}\) | Starting voltage | V |
| \(V_{min}\) | Minimum voltage | V |
| \(R_{ESR}\) | Equivalent series resistance | Ω |
| \(P\) | Constant load power | W |
| \(E\) | Energy stored at V_max | J |
| \(E_u\) | Usable energy between V_max and V_min | J |
| \(E_u/E\) | Usable fraction | - |
| \(t_0\) | Discharge time ignoring resistance | s |
| \(t\) | Discharge time with resistance | s |
| \(I_1\) | Starting current | A |
| \(I_2\) | Final current | A |
| \(E_{loss}\) | Energy lost in the resistance | J |
Method and standards
Capacitor energy balance.
Where it is used
- Ride-through and peak-power buffer sizing.
- Comparing with batteries and flywheels.
Common mistakes
- Using the full ½CV² as usable energy.
- Ignoring ESR at high power and low voltage.
Assumptions and limits
- Ideal capacitance (no voltage dependence or leakage).
References
- Capacitor energy and constant-power discharge with series resistance
Questions and answers
Why use only half the voltage?
Energy goes with V²: discharging to half voltage already releases 75 % of the energy, and the current at low voltage becomes very high.
Where are supercapacitors used?
Short, high-power duties: ride-through for drives and UPS, regenerative braking, pitch systems in wind turbines and grid frequency response.
What do the defaults represent?
An illustrative 150 F, 48 V bank with 6 mΩ resistance delivering 5 kW from 48 V down to 24 V.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004)