Worked example
Example: Illustrative 50 m3 tank, 250 W. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Heat leak into the tank | 0.25000 kW |
| Tank liquid volume | 50.000 m³ |
| Latent heat of vaporisation (446 kJ/kg at 1 atm) | 446.00 kJ/kg |
| Liquid density (70.8 kg/m³ at 1 atm) | 70.800 kg/m³ |
| Fill fraction | 90.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Boil-off rate | 2.0179 kg/h |
| Boil-off per day | 48.430 kg |
| Boil-off per day (fraction of contents) | 1.5201 % |
| Hydrogen in the tank | 3,186.0 kg |
| Time to boil off the contents | 65.785 d |
Open this example in the calculator and change any input.
Formula
\(\dot m_b = \frac{\dot Q}{h_{fg}}, \quad \frac{\dot m_b\cdot 1\,d}{\rho_lVf}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q\) | Heat leak into the tank | W |
| \(V\) | Tank liquid volume | m³ |
| \(h_{fg}\) | Latent heat of vaporisation (446 kJ/kg at 1 atm) | J/kg |
| \(\rho_l\) | Liquid density (70.8 kg/m³ at 1 atm) | kg/m³ |
| \(f\) | Fill fraction | - |
| \(\dot m_b\) | Boil-off rate | kg/s |
| \(\dot m_{day}\) | Boil-off per day | kg |
| \(\dot m/m\) | Boil-off per day (fraction of contents) | - |
| \(m\) | Hydrogen in the tank | kg |
| \(t_{empty}\) | Time to boil off the contents | s |
Method and standards
Cryogenic boil-off.
Where it is used
- Liquid hydrogen storage and transport.
- Insulation specification.
Common mistakes
- Ignoring ortho-para conversion heat.
- Assuming a sealed tank (pressure would rise instead).
Assumptions and limits
- Vented tank at constant pressure.
References
- Boil-off energy balance of a cryogenic tank
Questions and answers
Why is boil-off unavoidable?
Liquid hydrogen sits at −253 °C; no insulation is perfect, and every 446 J of leaked heat evaporates a gram.
Why do big tanks lose a smaller fraction?
Heat leak scales with surface area but contents with volume, so the loss fraction falls roughly with tank diameter.
What do the defaults represent?
An illustrative 50 m³ tank, 90 % full, with a 250 W heat leak.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.