Phase-Change Material (PCM) Thermal Storage Capacity

Heat stored in a phase-change material heated through its melting point, its volume and energy density, compared with water over the same range.

Food, dairy and textile

Inputs

Examples: Illustrative 1 t paraffin, 20-60 C, melt 50 CSalt hydrate 500 kg, 25-35 C, melt 29 CBelow melting only: 10-40 C, melt 58 C

Accepted: 0.1 to 100,000,000 kg
Accepted: -73.15 to 926.85 °C
Accepted: -73.15 to 926.85 °C
Accepted: -73.15 to 926.85 °C
Accepted: 0.1 to 5 kJ/(kg·K)
Accepted: 0.1 to 5 kJ/(kg·K)
Accepted: 1 to 1,000 kJ/kg
Accepted: 100 to 5,000 kg/m³

Results

Q = m[c_s(T_m − T₁) + L + c_l(T₂ − T_m)] when the range spans the melting point; sensible only otherwise. Water reference: 1,000 kg/m³ and 4,186 J/(kg·K). PCMs pay off when the useful temperature swing is small; heat transfer into the solid is usually the design limit.

Sensible heat (solid and liquid)14.000kWh
Latent heat0kWh
Total heat stored14.000kWh
PCM volume0.90909m³
Energy density (kWh per m³)15.400
Ratio to the same volume of water over the same range0.44147

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 1 t paraffin, 20-60 C, melt 50 C. The inputs, in the units selected above:

InputValue
PCM mass1,000.0 kg
Start temperature20.000 °C
End temperature60.000 °C
Melting temperature50.000 °C
Specific heat of the solid2.0000 kJ/(kg·K)
Specific heat of the liquid2.2000 kJ/(kg·K)
Latent heat of fusion200.00 kJ/kg
Mean density850.00 kg/m³

Applying the formula below gives:

ResultValue
Sensible heat (solid and liquid)22.778 kWh
Latent heat55.556 kWh
Total heat stored78.333 kWh
PCM volume1.1765 m³
Energy density (kWh per m³)66.583
Ratio to the same volume of water over the same range1.4316

Open this example in the calculator and change any input.

Formula

\(Q = m\left[c_s(T_m - T_1) + L + c_l(T_2 - T_m)\right], \quad \frac{Q}{Q_{water}} = \frac{Q}{\rho_wc_wV(T_2 - T_1)}\)

Variables

Symbol Meaning SI unit
\(m\) PCM mass kg
\(T_1\) Start temperature K
\(T_2\) End temperature K
\(T_m\) Melting temperature K
\(c_s\) Specific heat of the solid J/(kg·K)
\(c_l\) Specific heat of the liquid J/(kg·K)
\(L\) Latent heat of fusion J/kg
\(\rho\) Mean density kg/m³
\(Q_s\) Sensible heat (solid and liquid) J
\(Q_L\) Latent heat J
\(Q\) Total heat stored J
\(V\) PCM volume m³
\(Q/V\) Energy density (kWh per m³) -
\(Q/Q_{water}\) Ratio to the same volume of water over the same range -

Method and standards

Latent heat storage.

Where it is used

  • Solar and heat-pump buffer stores.
  • Building and cold-chain thermal storage.

Common mistakes

  • Counting latent heat when the range does not cross the melting point.
  • Ignoring subcooling and incomplete melting.

Assumptions and limits

  • Sharp melting point; constant properties.

References

  • Sensible and latent heat balance

Questions and answers

When is a PCM better than water?

When the temperature swing is small: across a 10 K window around its melting point a paraffin stores several times more heat per litre than water.

What limits PCM stores?

Low thermal conductivity of the solid slows charging and discharging; fins, capsules or graphite are added.

What do the defaults represent?

An illustrative 1 t of paraffin melting at 50 °C (200 kJ/kg), heated from 20 to 60 °C.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Twidell and Weir, Renewable Energy Resources, 2nd ed. (Taylor and Francis, 2006), Kothari, Singal and Ranjan, Renewable Energy Sources and Emerging Technologies, 2nd ed. (PHI, 2011)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.