FireCADCalc

Specific Energy Consumption and Saving against a Baseline

Specific energy consumption (energy per unit of product) for a baseline and current period, the improvement and the energy saved at current production.

Thermal power plantProcess steam and utilities

Inputs

Examples: Improved SECWorse SEC

Results

Normalise for weather, product mix and capacity use before claiming savings (ISO 50006 energy baselines).

Baseline SEC (energy per unit of product)6.0000GJ
Current SEC (energy per unit of product)6.4000GJ
Improvement-6.6667%
Energy saved at current production-20,000GJ

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Improved SEC. The inputs, in the units selected above:

InputValue
Baseline energy520,000 GJ
Baseline production100,000 -
Current energy540,000 GJ
Current production112,000 -

Applying the formula below gives:

ResultValue
Baseline SEC (energy per unit of product)5.2000 GJ
Current SEC (energy per unit of product)4.8214 GJ
Improvement7.2802 %
Energy saved at current production42,400 GJ

Open this example in the calculator and change any input.

Formula

\(SEC = \frac{E}{P}, \quad E_s = (SEC_0 - SEC_1)P_1\)

Variables

Symbol Meaning SI unit
\(E_0\) Baseline energy J
\(P_0\) Baseline production -
\(E_1\) Current energy J
\(P_1\) Current production -
\(SEC_0\) Baseline SEC (energy per unit of product) J per unit
\(SEC_1\) Current SEC (energy per unit of product) J per unit
\(\Delta SEC\) Improvement -
\(E_s\) Energy saved at current production J

Method and standards

Ratio method.

Where it is used

  • Energy management systems.
  • PAT and ISO 50001 reporting.

Common mistakes

  • Not normalising.
  • Mixing energy units.

Assumptions and limits

  • Comparable operating conditions; simple ratio method without regression normalisation (ISO 50006 baselines).
  • SEC is energy per unit of product in the same energy unit as the inputs.

References

  • SEC = energy/production; saving = (SEC₀ − SEC₁) × P₁ (ISO 50006 EnPI principle)

Questions and answers

520,000 GJ for 100,000 t, then 540,000 GJ for 112,000 t?

SEC 5.20 → 4.82 GJ/t: 7.3 % better, about 42,400 GJ saved.

Why not compare total energy?

Production rose; energy per unit shows real improvement.

PAT scheme?

Uses SEC with normalisation rules of its own.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators