Worked example
Example: 400 fittings 72 to 36 W. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Number of fittings | 400.00 - |
| Old fitting power (with gear) | 0.072000 kW |
| New fitting power | 0.036000 kW |
| Operating hours per year | 4,000.0 h |
| Electricity price per kWh | 8.0000 - |
| Installed cost per new fitting | 1,800.0 - |
| Grid factor (kg CO₂ per kWh) | 0.72000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Energy saved per year | 57.600 MWh |
| Cost saved per year | 460,800 |
| Simple payback (years) | 1.5625 |
| CO₂ avoided per year | 41.472 t |
Open this example in the calculator and change any input.
Formula
\(\Delta E = n(P_0 - P_1)t, \quad t_{pb} = \frac{n C_f}{\Delta E\, c}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(n\) | Number of fittings | - |
| \(P_0\) | Old fitting power (with gear) | W |
| \(P_1\) | New fitting power | W |
| \(t\) | Operating hours per year | s |
| \(c\) | Electricity price per kWh | - |
| \(C_f\) | Installed cost per new fitting | - |
| \(EF\) | Grid factor (kg CO₂ per kWh) | - |
| \(\Delta E\) | Energy saved per year | J |
| \(\Delta C\) | Cost saved per year | - |
| \(t_{pb}\) | Simple payback (years) | - |
| \(\Delta m\) | CO₂ avoided per year | kg |
Method and standards
Energy difference.
Where it is used
- Plant, office and street lighting.
- Energy audits.
Common mistakes
- Lamp watts without gear.
- Ignoring illuminance.
Assumptions and limits
- Same hours before and after. With no saving the payback is not shown.
References
- ΔE = n (P₀ − P₁) t
Questions and answers
400 fittings from 72 W to 36 W, 4000 h a year?
57,600 kWh, 460,800 a year; payback 1.6 years.
Old wattage?
Include the ballast or driver losses.
Controls?
Occupancy and daylight controls cut hours too.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.