FireCADCalc

Off-Load Tap Selection for a Target Secondary Voltage

Tap position on the HV winding to give a target secondary voltage under load from the actual supply voltage, tap step and range, and the resulting voltage.

Thermal power plantProcess steam and utilitiesSugar mill and cogeneration

Inputs

Examples: Illustrative 11 kV/433 V on 10.5 kV supplyHigh supply 11.4 kV33/11 kV, 1.25 % steps, low supply

Accepted: 0.1 to 800 kV
Accepted: 50 to 400,000 V
Accepted: 0.1 to 800 kV
Accepted: 50 to 400,000 V
Accepted: 0 to 20 %
Accepted: 0.5 to 5 %
Accepted: 1 to 20

Results

No-load secondary needed V_t/(1 − ε); ratio a = V_p/V_s0; tap = a/a_n − 1, rounded to the nearest step within ±n. Raising HV turns (positive tap) lowers the secondary voltage. Off-load tap changers must be moved de-energised; check light-load overvoltage after choosing a tap for full load.

Required tap (positive adds HV turns)-9.8182%
Selected tap position-8.0000
Resulting secondary voltage at load11,022V
Deviation from target0.20202%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 11 kV/433 V on 10.5 kV supply. The inputs, in the units selected above:

InputValue
Rated primary voltage11.000 kV
Rated secondary voltage (no load)433.00 V
Actual primary voltage10.500 kV
Target secondary voltage at load415.00 V
Voltage regulation at the load3.0000 %
Tap step2.5000 %
Taps either side of nominal2.0000 -

Applying the formula below gives:

ResultValue
Required tap (positive adds HV turns)-3.3931 %
Selected tap position-1.0000
Resulting secondary voltage at load411.20 V
Deviation from target-0.91600 %

Open this example in the calculator and change any input.

Formula

\(a_{req} = \frac{V_p(1 - \varepsilon)}{V_t}, \quad t_{req} = \frac{a_{req}}{a_n} - 1, \quad V_s = \frac{V_p(1 - \varepsilon)}{a_n(1 + ks)}\)

Variables

Symbol Meaning SI unit
\(V_{pn}\) Rated primary voltage V
\(V_{sn}\) Rated secondary voltage (no load) V
\(V_p\) Actual primary voltage V
\(V_t\) Target secondary voltage at load V
\(\varepsilon\) Voltage regulation at the load -
\(s\) Tap step -
\(n\) Taps either side of nominal -
\(t_{req}\) Required tap (positive adds HV turns) -
\(k\) Selected tap position -
\(V_s\) Resulting secondary voltage at load V
\(\Delta V/V_t\) Deviation from target -

Method and standards

Tap selection.

Where it is used

  • Commissioning distribution transformers.
  • Fixing persistent low or high voltage.

Common mistakes

  • Moving the tap the wrong way.
  • Ignoring light-load voltage rise.

Assumptions and limits

  • Taps on HV winding; constant regulation.

References

  • Turns-ratio adjustment by tapping

Questions and answers

Which way do I move the tap for higher secondary voltage?

Towards fewer HV turns (a negative or 'boost' tap); naming conventions vary, so check the rating plate.

Why include load regulation?

Secondary voltage drops under load; a tap chosen for no load leaves the load low.

What do the defaults represent?

An illustrative 11 kV/433 V transformer on a 10.5 kV supply, aiming for 415 V at load with 3 % regulation, ±2 taps of 2.5 %.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Harlow (ed.), Electric Power Transformer Engineering, 3rd ed. (CRC, 2012)

Related calculators