Worked example
Example: Illustrative 1 MWp, 1900 kWh/m2. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Temperature loss | 8.0000 % |
| Soiling loss | 2.0000 % |
| Shading loss | 2.0000 % |
| Mismatch and nameplate tolerance loss | 1.5000 % |
| DC wiring loss | 1.5000 % |
| Inverter efficiency (weighted) | 97.500 % |
| AC wiring and transformer loss | 1.5000 % |
| Availability | 99.000 % |
| Array rating (DC, at STC) | 1,000.0 kW |
| Annual irradiation on the array plane | 1,900.0 kWh/m² |
Applying the formula below gives:
| Result | Value |
|---|---|
| Performance ratio | 81.506 % |
| Total loss | 18.494 % |
| Specific yield (kWh per kWp per year) | 1,548.6 |
| Annual AC energy | 1,548.6 MWh |
| Capacity factor (AC energy over DC rating) | 17.666 % |
Open this example in the calculator and change any input.
Formula
\(PR = \prod_i(1 - l_i)\,\eta_{inv}A_v, \quad E_{AC} = P_{DC}\frac{H}{1\,\text{kW/m}^2}PR\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(l_T\) | Temperature loss | - |
| \(l_s\) | Soiling loss | - |
| \(l_{sh}\) | Shading loss | - |
| \(l_m\) | Mismatch and nameplate tolerance loss | - |
| \(l_{dc}\) | DC wiring loss | - |
| \(\eta_{inv}\) | Inverter efficiency (weighted) | - |
| \(l_{ac}\) | AC wiring and transformer loss | - |
| \(A_v\) | Availability | - |
| \(P_{DC}\) | Array rating (DC, at STC) | W |
| \(H\) | Annual irradiation on the array plane | J/m² |
| \(PR\) | Performance ratio | - |
| \(1 - PR\) | Total loss | - |
| \(Y_f\) | Specific yield (kWh per kWp per year) | - |
| \(E_{AC}\) | Annual AC energy | J |
| \(CF\) | Capacity factor (AC energy over DC rating) | - |
Method and standards
Loss-budget performance ratio.
Where it is used
- Energy yield estimates and contract guarantees.
- Diagnosing under-performing plants.
Common mistakes
- Adding losses instead of multiplying factors.
- Counting temperature loss twice (in PR and in the irradiation data).
Assumptions and limits
- Independent loss factors; annual averages.
References
- PV system loss factors and performance ratio
Questions and answers
What performance ratio is good?
About 0.80–0.85 for well-built modern plants; hot climates and dirty sites sit nearer 0.75.
Which loss is largest?
Usually temperature (5–12 % in warm climates), then inverter and soiling.
What do the defaults represent?
An illustrative 1 MWp plant with 1,900 kWh/m² per year on the array and typical losses: 8 % temperature, 2 % soiling, 2 % shading, 1.5 % mismatch, 1.5 % DC and AC wiring, 97.5 % inverter, 99 % availability.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9